12
5. Multi-step Speed and Auto-Program Operation Parameters
Set during running available
Parameter
Parameter functions
Setting range
Factory
setting
5-28
(Step 10 Time)
0 to 65500S
0
5-29
(Step 11 Time)
0 to 65500S
0
5-30
(Step 12 Time)
0 to 65500S
0
5-31
(Step 13 Time)
0 to 65500S
0
5-32
(Step 14 Time)
0 to 65500S
0
5-33
(Step 15 Time)
0 to 65500S
0
6. Protection Parameters
Set during running available
Parameter
Parameter functions
Setting range
Factory
setting
6-00
Over voltage stall prevention
function setting
0: Inactive
390
350-410V
6-01
Over current stall prevention
level setting
0: Inactive
170
20-200%
6-02
Over-torque detection (Mode
selection)
0: No detection
1: Over torque detection (OL2) during constant
speed running, continue to run after detection.
2: Over torque detection (OL2) during constant
speed running, stop running after detection.
3: Over torque detection (OL2) during
acceleration, continue to run after detection.
4: Over torque detection (OL2) during
acceleration, stop running after detection.
0
6-03
Over torque detection
(Detection level)
30 to 200%
150
6-04
Over torque detection time
0.1 to 10.0s
0.1
6-05
Electrical thermal overload
protection for Motor
(Select motor characteristics)
0: No action
1: Action in standard motor
2: Action in special motor
1
6-06
Electronic thermal relay
selection
30 to 600s
60
6-07
Alarm history (Latest)
0: No alarm records
1: OC (Over current)
2: OV(Over voltage)
3: OH(Over heating)
4: OL(Inverter overload)
5 :OL1(Motor overload)
6: EF(External fault)
7:
Reserved
8:
Reserved
9: OCA(
Over current in acceleration)
10: OCD(
Over current in deceleration)
11: OCN(
Over current in constant speed)
0
6-08
Alarm history (1
st
last)
0
6-09
Alarm history (2
nd
last)
0
6-10
Alarm history (3
rd
last)
0
6-11
Alarm history (4
th
last)
0
6-12
Alarm history (5
th
last)
0