EQJW146F001 EN
43
Appendix
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
10
Meter bus (only
with optional me-
ter bus- Modbus
gateway)
0
255
All
CO6 -> F10 - 1: Meter bus active
Function block parameters: (each WMZ1 to WMZ6)
Meter bus address / 0 to 255
Type code / 1434, CAL3,APAtO, SLS
Readout mode / 24h, CONT, CoiL for WMZ1 with “1434” and “CONT”
selection: tAr-A, tAr-E with time program
11
Flow rate limita-
tion in HC1 via
meter bus
0
1,5
m³/h
1,5
m³/h
1,5
m³/h
1
All
CO6 -> F11 - 1 only with - CO6 -> F10 - 1 CO5 -> F11 - 0
Function block parameters:
Maximum limit value /At, 0.01 to 650 m³/h
Maximum limit value heating operation* /At, 0.01 to 650 m³/h
Maximum limit value drinking water* / 0.01 to 650 m³/h
Limiting factor / 0.1 to 10
12
Power limitation
in HC1 via meter
bus
0
All
CO6 -> F12 - 1 only with - CO6 -> F10 - 1
- CO5 -> F10 - 0
Function block parameters:
Maximum limit value /At, 0.1 to 6500 kW
Maximum limit value heating operation* /At, 0.1 to 6500 kW
Maximum limit value drinking water* / 0.1 to 6500 kW
Limiting factor / 0.1 to 10
20
Modbus without
building
automation
system
0
All
CO6 > F20 - 1: Various Modbus specifications do not have any effect on the
collective level/building automation system reading
F Function block number, WE Default setting, Anl System code number
CO7: Device bus (all systems)
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
01
Device bus
0
All
CO7 -> F01 - 1: Device bus active
Function block parameters:
Device bus address/Auto
1)
, 1 to 32 (32)
1)
Auto = Automatic search for a free device bus address in the system
02
Clock synchroni-
zation
0
All
CO7 -> F02 - 1: controller sends its system time to all device bus participants
once every 24 hours
03
reserved
All
04
reserved
All
05
reserved
All