9

EGH130F931

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant.  
This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
 supply  voltage. 

The output signal is to be tapped by a measuring instrument. Output 
 voltage is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

, the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for 
ground wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it. 

Therefore, pay attention to correct wiring!

Connecting scheme 

Parallel operation

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Connecting scheme 

Individual operation

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Summary of Contents for EGH130F931

Page 1: ...urf hler 2 Aufputz kalibrierf hig mit aktivem Ausgang G Operating Instructions Mounting Installation Room humidity and temperature sensors 2 on wall calibratable with active output F Notice d instruct...

Page 2: ...n the groove at centre press down and lift up the bottom frame slightly Pull top cover for ward and hold it Pour ouvrir le bo tier placer le tournevis 2 0 au centre de l encoche pousser vers le bas et...

Page 3: ...ich TECHNISCHE DATEN Spannungsversorgung 24 V AC 20 und 15 36 V DC Lastwiderstand RL 5 kOhm Leistungsaufnahme 1 1 VA 24 V DC 2 2 VA 24 V AC Sensoren digitaler Feuchtesensor mit integriertem Temperatur...

Page 4: ...1 0 10 2 0 15 3 0 20 4 0 25 5 0 30 6 0 35 7 0 40 8 0 45 9 0 50 10 0 Anschlussbild Ausgang 0 10 V D EGH130F931 Rev 2021 V23 1 2 3 4 230V AC 24V AC DC SPS PC UB 24V AC DC Ausgang Feuchte r H 0 10V Ausg...

Page 5: ...g ge messen Wird dieses Ger t mit DC Versorgungsspannung betrieben ist der Betriebsspannungseingang UB f r 15 36 V DC Einspeisung und UB bzw GND als Masseleitung zu verwenden Werden mehrere Ger te von...

Page 6: ...verlegung zu stromf hrenden Leitungen zu vermeiden und die EMV Richtlinien zu beachten Dieses Ger t ist nur f r den angegebenen Verwendungszweck zu nutzen dabei sind die entsprechenden Sicherheitsvors...

Page 7: ...ble TECHNICAL DATA Power supply 24 V AC 20 and 15 36 V DC Load resistance RL 5 kOhm Power consumption 1 1 VA 24 V DC 2 2 VA 24 V AC Sensors digital humidity sensor with integrated temperature sensor s...

Page 8: ...C C UA in V 0 0 0 5 1 0 10 2 0 15 3 0 20 4 0 25 5 0 30 6 0 35 7 0 40 8 0 45 9 0 50 10 0 Connecting diagram Output 0 10 V 4 wire connection Schematic diagram 1 2 3 4 230V AC 24V AC DC PLC PC UB 24V AC...

Page 9: ...ge supply it is to be ensured that all positive operating voltage input terminals of the field devices are connected with each other and all negative operating voltage input terminals reference potent...

Page 10: ...rallel with current carrying lines is to be avoided and EMC directives are to be observed This device shall only be used for its intended purpose Respective safety regulations issued by the states the...

Page 11: ...ustage fin peut tre effectu par l utilisateur CARACT RISTIQUES TECHNIQUES Alimentation en tension 24 V ca 20 15 36 V cc R sistance de charge RL 5 kOhm Puissance absorb e 1 1 VA 24 V cc 2 2 VA 24 V ca...

Page 12: ...mesure 0 50 C C UA en V 0 0 0 5 1 0 10 2 0 15 3 0 20 4 0 25 5 0 30 6 0 35 7 0 40 8 0 45 9 0 50 10 0 Sch ma de raccordement Sortie 0 10 V Raccordement 4 fils Sch ma de raccordement 1 2 3 4 230V AC 24V...

Page 13: ...ls sont aliment s en 24V ca il faut veiller ce que toutes les entr es de tension positives des appareils de terrain soient reli es entre elles de m me que toutes les entr es de tension n gatives poten...

Page 14: ...oser les c bles de sondes en parall le avec des c bles de puissance les directives CEM sont respecter Cet appareil ne doit tre utilis que pour l usage qui est indiqu en respectant les r gles de s curi...

Page 15: ...nsione di alimentazione 24 V AC 20 e 15 36 V DC Carico ammissibile RL 5 kOhm Potenza assorbita 1 1 VA 24 V DC 2 2 VA 24 V AC Sensori sensore di umidit digitale con sensore di temperatura integrato bas...

Page 16: ...15 3 0 20 4 0 25 5 0 30 6 0 35 7 0 40 8 0 45 9 0 50 10 0 I EGH130F931 Rev 2021 V23 Schema di collegamento Uscita 0 10 V Collegamento a 4 conduttori Schema di comando 1 2 3 4 230V AC 24V AC DC PLC PC...

Page 17: ...r l alimentazione 15 36 V DC e l ingresso UB o GND per la terra Quando pi dispositivi sono alimentati da un unica alimentazione con ten sione 24 V AC necessario assicurarsi che tutti i terminali di in...

Page 18: ...zare cavi schermati evitare la posa in parallelo delle linee conduttrici di corrente e rispettare le norme di compatibilit elettromagnetica Utilizzare questo apparecchio esclusivamente allo scopo indi...

Reviews: