background image

4 INT-KNX 

SATEL 

Switches 1-5 are used for setting the module address

. The address must be different 

than that in the other modules connected to the expander bus. The address is the sum of 
numerical values set on the switches 1-5 (see Table 1). 

Switches 6-8 allow you to specify the number of outputs that will be added to the 
system.

 The numerical value (see Table 1) to which the desired number of outputs 

corresponds (see Table 2) must be set on the switches. 

Note:

 If the number of outputs set on the switches is higher than the available one, the 

correct identification of the module by the control panel will be impossible. In order to 
determine what number of outputs is available in the system, subtract the main board 
outputs and the outputs in expanders connected to the control panel from the 
maximum number of outputs supported by the panel. 

 

Numerical value 

0 1 2 3 4 5 6 7 

Number of outputs 

8  16 24 32 40 48 56 64 

Table 2. The relationship between the numerical value set on the switches 6-8 and the 

number of outputs that will be assigned to the INT-KNX module. 

 
 

 

Fig. 4. Examples of the DIP switch setting.  

A – address: 5, number of outputs: 8. B – address: 22, number of outputs: 24. 

 
1 address is allocated for each group of 8 outputs on the expander bus. The module can 
occupy up to 8 addresses on the expander bus. The control panel assigns consecutive 
addresses to the module after the address set on the DIP switches. This should be taken into 
consideration when designing the system and a sufficient number of free addresses should 
be left. If the number of free addresses is insufficient, it will be impossible to properly 
complete the identification procedure. 

3. Module identification 

The control panel does not support the modules which have not been identified, therefore 
you must run the identification function after completion of the installation and power-up of 
the alarm system. You can do it by means of: 

  LCD keypad: S

ERVICE MODE

 

X

S

TRUCTURE

 

X

H

ARDWARE

 

X

I

DENTIFICATION

 

X

E

XPANDERS ID

.; 

  D

LOAD

X program: "Structure" window 

Æ

"Hardware" tab 

Æ

"Expansion modules" branch 

Æ

"Exp. modules identification" button. 

During the identification procedure, a number of outputs in the system, determined by means 
of DIP switches, is assigned to the module, and additional addresses are allocated if the 
number of outputs is greater than 8. 
The control panel controls presence of the identified modules. Disconnecting the module 
from the bus, changing the DIP switch position or swapping for another module with the 
same DIP switch settings will trigger an alarm. 

Summary of Contents for INT-KNX

Page 1: ...support for On and Off commands RS 232 port for connecting the module to the BCU Dedicated adapter interface and cable for connecting the module to the BCU 2 Installation Disconnect power before maki...

Page 2: ...battery presence by periodically lowering the voltage make sure that the battery is present for correct operation of the INT KNX module 6 Install and connect the BCU to the KNX bus in accordance with...

Page 3: ...ion with the control panel 3 male socket DB 9 RS 232 port to connect the module to the Bus Coupling Unit BCU using the cable included in the delivery set Description of terminals TMP tamper circuit in...

Page 4: ...outputs 24 1 address is allocated for each group of 8 outputs on the expander bus The module can occupy up to 8 addresses on the expander bus The control panel assigns consecutive addresses to the mo...

Page 5: ...e module with the DLOADX program use the Read button to read data from the module see Fig 5 The program can suggest reading the data itself when you click on the module name in the Structure window Ha...

Page 6: ...sent after activating deactivating the output Telegram type depending on the selected telegram type 0 Toggle on activating the output a telegram with On command is sent and on deactivating the output...

Page 7: ...the Off command by the INT KNX module and the zone restore will occur on receiving a telegram with the On command Note The data are not read from written to the module when using the and buttons in t...

Page 8: ...The declaration of conformity may be consulted at www satel eu ce SATEL sp z o o ul Schuberta 79 80 172 Gda sk POLAND tel 48 58 320 94 00 info satel pl www satel pl...

Reviews: