18 GPRS-T6
SATEL
– telephone damage.
Additional information about the trouble is provided by the LEDs on the electronics
board (see Fig. 3).
4.3.4 “Inputs” tab
Fig. 9. “Inputs” tab.
Inputs
The table enables programming the working parameters of Z1 ÷ Z8, BTE, TMP and ACE
inputs.
For the ACE input, it is only possible to program the "Sensitivity" parameter (values up
to 99 minutes and 59 seconds can be entered) and define whether and how it is to
control the output.
Type
– the input can be programmed as:
– digital, NC type – enter digit 1,
– digital, NO type – enter digit 2,
– analog – enter digit 3,
– disabled – enter digit 0.
Sensitivity
– time during which:
– the NC type digital input must be disconnected from the ground so that the module can
register the input violation,
– the NO type digital input must be shorted to ground so that the module can register
the input violation,
– voltage on the analog input must drop below threshold L (minus tolerance) or rise above
threshold H (plus tolerance) so that the module can register exceeding the preset value
(see Fig. 10).
Values from the 0 to 5100 ms range can be programmed (every 20 ms).
Restore
– time during which:
– the NC type digital input must be again shorted to ground so that the module can
register input restore,
– the NO type digital input must be again disconnected from the ground so that
the module can register input restore,