Arming

 [Reader A arm./Reader B arm.] – this option defines whether the partition can be 

armed by using the DALLAS chip. Hold the chip at the reader to arm the partition. 

INTEGRA

 

Hardware signaling of readout 

– activation of this option will start the chip code readout 

signaling which is independent of the control panel. 

INTEGRA

 

Alarm – 3 incorrect codes 

– with this option enabled, alarm will be generated after three 

attempts to read in an invalid DALLAS chip. 

INTEGRA

 

Control BI

 

output

 – reading the code of chip assigned to the "

Bi output control

" type of 

codes will control the output type 25 (BI

 

S

WITCH

) in the given partition (if the code is 

authorized to access the given partition and is included in the list of module users). 

Control MONO

 

output

 – reading the code of chip assigned to the 

"Mono output control

" type 

of codes will control the output type 24 (MONO

 

S

WITCH

) in the given partition (if the 

code is authorized to access the given partition and is included in the list of module 
users). 

Partition blocking

 – reading the chip of the guard or a user having the 

"Temporary partition 

blocking" 

type of code

 

when the partition is armed will temporarily block the time of 

entry in the partition the module is assigned to. The bypass duration is determined in 
the partition parameters (for the guard) or in the user code parameters. 

Guard control

 – reading the chip of the user having the "

Guard

" type of code will be 

recorded as completion of the round. 

Signaling 

– options related to signaling by LEDs of the reader or by the buzzer connected to 

expander. 

INTEGRA

 

Alarm signaling (fixed time) 

– acoustic alarm signaling in the given partition (through the 

total duration of alarm). 

Alarm signaling (until canceled) 

[Alarm (latch)] – acoustic alarm signaling in the given 

partition until the alarm is cleared. 

Signaling entry delay 

– acoustic signaling of the countdown of entry delay time. 

Signaling exit delay 

– acoustic signaling of the countdown of exit delay time. 

Auto-Arm delay countdown 

– acoustic signaling of auto-arming delay countdown in the 

group to which the module is assigned. 

No auto-reset after 3 tampers 

– each expander will automatically disable its tamper alarm 

function after three consecutive (not cleared) tamper detection alarms, which prevents 
the same events from being saved repeatedly in the control panel memory. This option 
allows the blocking function to be deactivated. 

Open door if fire 

[Doors on fire] – control mode for the door blocking during fire alarm: 

 

no 

– fire alarm has no effect on the door blocking, 

 

Partition fire alarm 

– fire alarm in the partition will unblock the door controlled by the 

module, 

 

Object fire alarm 

– fire alarm in the object will unblock the door controlled by the 

module, 

 

fire alarm 

– fire alarm in the system will unblock the door controlled by the module. 

6. Signaling 

The mode of acoustic/optical signaling is conditional upon the alarm control panel program. 
The expander has two outputs to control the LEDs' status and one output to control audible 
signaling. The DALLAS chip readers come with a built-in two-color LED. It is also possible to 
connect extra LEDs or a buzzer to the expander. 

Summary of Contents for CA-64 DR

Page 1: ...e in the module functions is possible only in case of interact with control panels of INTEGRA 1 Module description Figure 1 Diagrammatic view of the module electronics board Legend 1 LED indicator of...

Page 2: ...should be shorted to ground DRZWI door status control input NC if not used it should be shorted to ground The RESET pins are used in the manufacturing process and should not be shorted 1 1 DIP switch...

Page 3: ...nostable switch the leads of that button are to be connected to the terminals ON and COM 7 Connect the leads of the tamper contact on expander housing to the terminals TMP and COM Where two expanders...

Page 4: ...ing devices ventilation pumps etc The mode of relay operation depends on the programmed function disarm the system and clear alarms Disarming alarm clearing takes place when the reader is touched with...

Page 5: ...hip readers Name the option to give an individual 16 character name to the module This option can be accessed in the LCD keypad as follows Service mode Structure Hardware Expanders Names expander sele...

Page 6: ...ition to which the module is assigned is armed unauthorized opening of the door will trigger the alarm and can be additionally signaled on the output type 94 ALARM UNAUTHORIZED DOOR OPENING Max door o...

Page 7: ...ling options related to signaling by LEDs of the reader or by the buzzer connected to expander INTEGRA Alarm signaling fixed time acoustic alarm signaling in the given partition through the total dura...

Page 8: ...g situations can be signaled acoustically Alarm in partition continuous beep Fire alarm one long beep every second Countdown of entry delay short beeps every 3 seconds Countdown of exit delay long bee...

Page 9: ...V 14V DC Maximum current consumption without heads 70mA Maximum relay switchable voltage AC 250V Maximum relay switchable current 2A Environmental class II Operating temperature range 10 C 55 C Dimens...