terminal is isolated. On actuation of the relay, the C terminal becomes shorted to the 
NO terminal, and the NC terminal becomes cut off (which is signaled by the LED going 
on). 

Description of terminals: 
+12V

 

–  power supply input 

CLK

DTA

 – expander bus 

COM

 – 

common 

ground 

TMP

 

–  module tamper detection input (NC) – if not used, it should be shorted to 

ground. 

 

C

NC

NO

 – relay terminals 

 

SIGA 

–  data input, head A 

SIGB 

–  data input, head B 

BPA

 

– sound signaling control, head A – for the acoustic signaling to work it is 

necessary to connect the sounder (buzzer) to the terminal 

BPB

 

– sound signaling control, head B – for the acoustic signaling to work, it is 

necessary to connect the sounder (buzzer) to the terminal 

LD1A 

–  LED green color control, head A  

LD1B

 

–  LED green color control, head B 

LD2A

 

–  LED red color control, head A 

LD2B 

–  LED red color control, head B 

+GA

 

–  not used 

+GB

 

–  not used 

DISA

 

–  not used 

DISB

 

–  not used 

ON

 

–  relay control input (NC) – if not used, it should be shorted to ground. 

DRZWI

 

–  door status control input (NC) – if not used, it should be shorted to ground. 

 

The RESET pins

 are used in the manufacturing process and should not be shorted. 

1.1  DIP switches  

By using the DIP switches you can set an individual address of device. The address should 
be set with the switches from 1 to 5. This address must differ from those of the other modules 
connected to the control panel expander bus. In order to determine the expander address, 
add up the numbers set on particular DIP switches, according to Table 1. 

Switch 

number 

1 2 3 4 5 

Numerical equivalent

  

(for switch in ON position) 

1 2 4 8 16 

Table 1. 

The five switches allow addresses to be assigned to 32 expanders (numbers from 0 to 31). 
Addresses of the expanders connected to one bus may not be repeated, while the 
addressing sequence is optional. It is recommended that you assign consecutive addresses, 
starting from zero, to expanders and other modules connected to one bus. This will permit 
problems to be avoided during extension of the alarm system. 
Position of the switches 6 and 7 is irrelevant. 

The switch 8 must be set in ON

 

position.

 

Summary of Contents for CA-64 DR

Page 1: ...e in the module functions is possible only in case of interact with control panels of INTEGRA 1 Module description Figure 1 Diagrammatic view of the module electronics board Legend 1 LED indicator of...

Page 2: ...should be shorted to ground DRZWI door status control input NC if not used it should be shorted to ground The RESET pins are used in the manufacturing process and should not be shorted 1 1 DIP switch...

Page 3: ...nostable switch the leads of that button are to be connected to the terminals ON and COM 7 Connect the leads of the tamper contact on expander housing to the terminals TMP and COM Where two expanders...

Page 4: ...ing devices ventilation pumps etc The mode of relay operation depends on the programmed function disarm the system and clear alarms Disarming alarm clearing takes place when the reader is touched with...

Page 5: ...hip readers Name the option to give an individual 16 character name to the module This option can be accessed in the LCD keypad as follows Service mode Structure Hardware Expanders Names expander sele...

Page 6: ...ition to which the module is assigned is armed unauthorized opening of the door will trigger the alarm and can be additionally signaled on the output type 94 ALARM UNAUTHORIZED DOOR OPENING Max door o...

Page 7: ...ling options related to signaling by LEDs of the reader or by the buzzer connected to expander INTEGRA Alarm signaling fixed time acoustic alarm signaling in the given partition through the total dura...

Page 8: ...g situations can be signaled acoustically Alarm in partition continuous beep Fire alarm one long beep every second Countdown of entry delay short beeps every 3 seconds Countdown of exit delay long bee...

Page 9: ...V 14V DC Maximum current consumption without heads 70mA Maximum relay switchable voltage AC 250V Maximum relay switchable current 2A Environmental class II Operating temperature range 10 C 55 C Dimens...

Page 10: ...est EC declarations of conformity and certificates are available for downloading on the website www satel pl SATEL sp z o o ul Schuberta 79 80 172 Gda sk POLAND tel 48 58 320 94 00 info satel pl www s...

Reviews: