8.  Starting the module 

Note:

  In systems having expansion modules with their own power supply, it is recommended 

to start the panel first, and then the other components of the system. 

1.  Switch on power supply of the alarm system and the expander (the LED which indicates 

communication with the alarm control panel will flash with steady light). 

2.  Call the "

Expander identification

" function in the LCD keypad

 

(

Æ

Service mode 

Æ

Structure 

Æ

Hardware 

Æ

Identification). Having identified the CA-64 ADR expander, control panel 

will automatically identify the CA-64 

ADR 

MOD addressable modules. When the 

identification is completed, the LED indicator of communication with the control panel will 
start blinking. After identification, all the 

new

 zones are programmed to factory defaults, 

the detector type being set to zero (no detector). 

Notes: 

 

In the process of identification, the control panel writes to the module memory a special 
(16-bit) number intended to detect the module presence in the system. Replacement of the 
expander with another (even one having the same address set up on the switches) without 
a new identification will trigger alarm (module tamper - verification error). 

 

Extension of the alarm system by new zones (addressable detectors), which so far have 
not been used, will require an identification of the expanders. 

3.  Using the DLOAD64 / DLOADX program or LCD keypad, set the zone parameters (refer 

to the CA-64 ADR MOD addressable module manual). 

4.  End the service mode operation, saving data in the FLASH memory. 

9. Technical data 

Expander supply voltage...................................................................................... 17V...24V AC 
Internal power supply output voltage, rated ................................................... 13.6V...13.8V DC 
Current efficiency ............................................................................................................... 2.2A 
POW output current-carrying capacity ............................................................................... 1.5A 
Battery charging current (switchover) .............................................................. 350mA / 700mA 
Dimensions of CA-64 ADR module electronics board............................................. 68x140 mm 
Number of handled addressable detectors (zones) ...............................................................48 
CA-64 ADR MOD module current consumption...............................................................1.2mA 
 

The latest EC declaration of conformity and product approval certificates 

are available for downloading on website   

www.satel.pl

 

 

 
 

SATEL sp. z o.o. 

ul. Schuberta 79 

80-172 Gda

ń

sk 

POLAND 

tel. + 48 58 320 94 00 

[email protected] 

www.satel.pl 

Summary of Contents for CA-64 ADR

Page 1: ...ed battery Note Installation of the CA 64 ADR expander in the CA 64 alarm system will exclude the option to install other zones expanders as well as the CA 64 PP zone output expander This manual has b...

Page 2: ...connect windings of the secondary mains transformer The minimum input voltage at the maximum load of the transformer by the module can be 16V AC 2 Operation description Operation of the expander consi...

Page 3: ...der then during the identification procedure addresses 30 31 and also 0 1 and 2 will be additionally assigned to the module Should these addresses be already taken the control panel would be unable to...

Page 4: ...module Note Do not set the same addresses in the CA 64 ADR MOD modules because the detectors having such modules will have the same zone number assigned in the system 4 1 Interaction with the CA 64 co...

Page 5: ...signed to the keypad zones 29 32 zones assigned to the detectors with addressable zones installed detector with address 20 zone 29 detector with address 21 zone 30 etc In order to obtain continuity of...

Page 6: ...600m 3 Table 4 Fig 5 Connecting of addressable detectors to internal expander bus Fig 6 Example of connecting the addressable detector without tamper control 6 Installation The addressable zones expan...

Page 7: ...Connect the leads of internal data bus to the inputs INT 12V and COM and connect the addressable detectors to the bus If current consumption by the addressable detectors and battery exceeds capacity o...

Page 8: ...e module presence in the system Replacement of the expander with another even one having the same address set up on the switches without a new identification will trigger alarm module tamper verificat...

Reviews: