background image

CA-64 ADR 

SATEL 

3

Switch 

number 

1 2 3 4 5 

Numerical equivalent

  

(for switch in ON position)

 

1 2 4 8 16 

Table 1. 

Five switches allow addresses to be assigned to 32 expanders (numbers from 0 to 31). 
Addresses of the expanders connected to one bus can not be repeated. It is recommended 
that you assign consecutive addresses, starting from zero, to expanders and other modules 
connected to one bus. This will permit problems to be avoided during extension of the alarm 
system. 
 
 
 
 
 
 
 

Fig. 2. Example of DIP switch settings - interaction with the CA-64 control panel. 

 
 
 
 
 
 
 

Fig. 3. Example of DIP switch settings - interaction with the INTEGRA control panel. 

3.1  Interaction with the CA-64 control panel (switch 8 in OFF position) 

When interfacing with the CA-64 control panel, the CA-64 ADR expander will always take up 
6 addresses on the expander bus, i.e. the address set in the expander and 5 consecutive 
ones. For example, if  address 0 has been set in the module, addresses 1 to 5 will be 
additionally assigned to the expander during the identification procedure. It should be borne 
in mind, that if e.g. address 29 is set in the expander, then, during the identification 
procedure, addresses 30, 31, and also 0, 1 and 2 will be additionally assigned to the module. 
Should these addresses be already taken, the control panel would be unable to correctly 
complete the identification procedure. 

3.2 Interaction 

with 

the 

INTEGRA control panels (switch 8 in ON position) 

When interfacing with the INTEGRA control panel, the CA-64 ADR expander can take from 1 
to 6 addresses on the expander bus. Which addresses will be reserved by the control panel 
depends on the number of connected detectors with installed CA-64 ADR MOD  modules, 
and on the addresses set in those modules (see Table 2). For each group of 8 addresses of 
the CA-64 ADR MOD modules, 1 address on the expander bus and 8 zones in the system 
are reserved. Remember, however, that having even one detector with installed CA-
64 ADR MOD module, in which an address from any group of 8 addresses is set, will take up 
an address on the expander bus and reserve 8 zones in the system. Therefore, it is advisable 
that you set consecutive numbers with no skips in the CA-64 ADR MOD modules. Thus you 
can avoid blocking of the expander bus addresses, as well as the control panel zone 
numbers, which can be used by other expanders. 
 

address:

control panel type: 

CA-64 

address:

22 

control panel type: 

INTEGRA 

Summary of Contents for CA-64 ADR

Page 1: ...ed battery Note Installation of the CA 64 ADR expander in the CA 64 alarm system will exclude the option to install other zones expanders as well as the CA 64 PP zone output expander This manual has b...

Page 2: ...connect windings of the secondary mains transformer The minimum input voltage at the maximum load of the transformer by the module can be 16V AC 2 Operation description Operation of the expander consi...

Page 3: ...der then during the identification procedure addresses 30 31 and also 0 1 and 2 will be additionally assigned to the module Should these addresses be already taken the control panel would be unable to...

Page 4: ...module Note Do not set the same addresses in the CA 64 ADR MOD modules because the detectors having such modules will have the same zone number assigned in the system 4 1 Interaction with the CA 64 co...

Page 5: ...signed to the keypad zones 29 32 zones assigned to the detectors with addressable zones installed detector with address 20 zone 29 detector with address 21 zone 30 etc In order to obtain continuity of...

Page 6: ...600m 3 Table 4 Fig 5 Connecting of addressable detectors to internal expander bus Fig 6 Example of connecting the addressable detector without tamper control 6 Installation The addressable zones expan...

Page 7: ...Connect the leads of internal data bus to the inputs INT 12V and COM and connect the addressable detectors to the bus If current consumption by the addressable detectors and battery exceeds capacity o...

Page 8: ...e module presence in the system Replacement of the expander with another even one having the same address set up on the switches without a new identification will trigger alarm module tamper verificat...

Reviews: