Station  does  not  receive  or  acknowledge  the  codes  sent  by  the  panel

  – wrongly 

selected  format,  inadequate  identifier  length  (3  characters,  while  the  station  requires  4), 
inadequate  event  code  length  (1  character,  while  the  station  requires  2)  or  low  quality  of 
telephone connection.

 

Note

:  For  the  Ademco  Express  transmission  format,  the  identifier  „0000”  is  valid  (sending 

zeroes  is  possible),  however  it  is  not  valid  with  the  other  formats  (sending  zeroes  is 
impossible).

 

A headset connected to the "telephone line monitoring" jack in the SM-2 synthesizer can be 
helpful in analyzing the problems with communication to the monitoring station. 
Connection with the station is established in the following way: 

  the  station  answers  the  call  and  sends  the,  so-called,  handshake  signal  (one  or  a  few  in 

sequence if the station supports several transmission formats), 

  the  control  panel  recognizes  the  station  handshake  signal  and  if  it  matches  the 

programmed  transmission  format,  the  control  panel  answers  by  sending  identifier  and 
event code in appropriate tones (once or twice, depending on the selected format) – in the 
headset  connected  to  the  line  monitoring  jack,  these  sounds  are  much  louder  than  the 
monitoring station signals, 

  if  the  station  receives  information,  it  will  acknowledge  it  with  the  same  signal  as  the 

handshake, 

  the  panel  disconnects  or  sends  next  codes  if  there  still  are  some  other  events  to  be 

reported to the station. 

The  most  common  monitoring  problems  result  from  inaccurate  information  on  the 
transmission formats supported by the given station (e.g., ambiguous names of the formats), 
errors  in  the  data  entered  into  the  control  panel,  as  well  as  poor  quality  of  the  telephone 
connections.  Often  only  by  “monitoring”  process  of  communication  you  are  able  to  find  the 
cause of a problem.  

Note:

  Some stations do not acknowledge reception of the event code if it has another format 

(e.g., 4/1 instead of the required 4/2). If this is the case, the control panel will repeat its 
attempts  to  establish  communication,  while  telephones  in  the  facility  will  be 
disconnected – the costs of such connections may be very high. For this reason, it is 
recommended that all the programmed codes be very carefully checked. It is possible 
to  activate  the  options  7  and  8  in  FS47,  which  makes  the  panel  ignore  the  codes 
unacknowledged  in  16  consecutive  retries.  Problems  of  this  type  do  not  occur  in 
professional, multi-format monitoring stations (including the Satel STAM-1). 

Downloading – communication with computer  

Programming the control panel through RS TTL serial port 

The  programming  is  possible  with  the  use  of  a  special  cable  (see:  p. 12).  To  run  the 
software,  select  a  suitable  COM  port  number  in  the  DLOAD10  program  (“Configuration” 
window).  Then,  from  the 

“Communication”

  menu,  select  the 

“Local  connection 

with...”

,  and,  subsequently,  select  the  control  panel  type  (e.g.

  “

CA6v5 - RS-232(TTL)”). 

Activate the service function FS112 in the control panel. Consistency is required between 
the  panel  and  the  computer  communication  codes  (FS2  and FS3)  programmed  in  the 
panel and included in the DLOAD10 program data. 

Programming with the use of modem 

Telephone  communication  with  the  computer  requires  a  modem.  The  modem  must  meet 
two essential conditions:  

Summary of Contents for CA-6-P

Page 1: ...Firmware Version 6 06 GDA SK ca6i_en 05 09 INSTALLER MANUAL...

Page 2: ...a fully discharged battery with voltage on unloaded terminals less than 11 V to the alarm panel In order to avoid equipment damage the fully discharged never used battery should be precharged by means...

Page 3: ...of Telephone Line 20 Connection of Voice Synthesizer 20 Connection of power supply 20 Starting the control panel 21 Entering service mode from pins 22 ACTIVATING SELECTED FUNCTIONS 22 Guard control f...

Page 4: ...s of telephone exchange signals which enables an alarm voice message to be sent after answering the call support of NOKTON radio messaging in PC16OUT format built in port RS 232 TTL the RJ socket is p...

Page 5: ...lation counters a zone violation code is sent to the station until the number of violations specified for that counter is exceeded programming in FS7 Then the violation triggers an alarm a zone alarm...

Page 6: ...olation of this zone during countdown of the exit delay will trigger an alarm Reaction time for each zone can be programmed within 0 016 s to 4 08 s For delayed zones an individual time delay can be s...

Page 7: ...larms the output starts on detecting any keypad alarm The output can remain active for a specified time from 01 to 99 seconds or from 01 to 99 minutes or until the alarm is cleared by the user During...

Page 8: ...mited to indicating the exit delay for specified partition 17 entry delay status the output is active during the entry delay countdown Operation of the output can be limited to selecting the entry del...

Page 9: ...med mode it functions similarly to the ARM STATUS output but it is activated right after exit delay starts not after changeover from the exit delay to the armed mode it can be used for example as indi...

Page 10: ...e one left by the deleted user Individual users may have the following authority levels 1 accessible all functions except creating and deleting users 2 accessible arming and disarming change of access...

Page 11: ...onnected to the station the control panel will suspend dialing the station number for 60 seconds and if the message is also to be transmitted by the dialer it will make the line available to the diale...

Page 12: ...top dialing the number for which connection cannot be established no answer permanently busy etc Messaging can be carried on until successful It is also possible to determine the maximum number of ret...

Page 13: ...e control panel Notification of the monitoring station will take place after communication with the computer is over 3 Establishing of communication from the control panel by calling the function 0 by...

Page 14: ...connected with a special cable manufactured by SATEL The cable includes a converter changing the signal into a standard corresponding to the RS 232 port in the computer 12 V 12 V The data can be tran...

Page 15: ...l system the stabilized voltage of the control panel power supply is 13 6 V to 13 8 V and is factory set battery status monitoring system with optional disconnection of the battery if discharged durin...

Page 16: ...n of the housing be careful so as not to damage the wires which will be passed through the hole in its back panel When the housing is secured you can install the control panel main board and proceed t...

Page 17: ...e inputs The keypad Z1 terminal is treated as zone 7 Z2 as zone 8 Provision is made for connecting additional keypads in parallel with the first one Each keypad should be connected to the control pane...

Page 18: ...nables the status of detector and its tamper contact to be monitored at the same time The detectors may be supplied from any of the electronically protected outputs OUT1 to OUT3 The output should be p...

Page 19: ...M 12V C TMP EOL NO 2 2k Fig 7 Example of connecting NO type detector in EOL configuration to control panel COM OUT3 DTA CLK CTL COM Z1 Z2 Z3 COM Z4 KPD COM CA 6 EOL NC 2 2k NC TMP COM 12V NC TMP Fig 8...

Page 20: ...T2 COM OUT3 COM 12 V LIMITER 2 2A LIMITER 2 2A LIMITER 2 2A LOAD LOAD LOAD KPD LIMITER 1 5A Fig 10 Connection of a load to high current outputs In the case of sirens which alarm after power is supplie...

Page 21: ...tter NEMROD system format PC16OUT In such a case it is necessary to change the operating mode of these outputs by activating a suitable option in the service function 5 During operation with the NOKTO...

Page 22: ...multicore cable This may result in damage to the system in case of a high voltage punch through from the telephone line Telephone terminals of the panel should be connected to PSTN analog lines only C...

Page 23: ...avoiding damage to the security system elements caused by possible installation faults Note Should it be necessary to completely disconnect the control panel power supply the mains and the battery re...

Page 24: ...he user passwords FS110 and or reset the event log FS108 Note Shorting the pins and power up alone will restore no parameters These operations will call up the service mode thus making it possible to...

Page 25: ...en the above parameters are correctly programmed and the alarm is triggered the on board LED designated as DIALER should go on which indicates that the panel has started telephone messaging with pulse...

Page 26: ...he list from the monitoring station operator the codes can be one digit the other character being 0 or two digit as required by the station the codes with inappropriate length may block communication...

Page 27: ...e transmission formats supported by the given station e g ambiguous names of the formats errors in the data entered into the control panel as well as poor quality of the telephone connections Often on...

Page 28: ...P mainboard Fig 14 Connecting control panel to modem for local mode programming Local communication connect the computer modem to the TIP and RING control panel terminals the telephone line must be di...

Page 29: ...s initialization error wrong command initializing the modem Correct initialization of the modem does not mean it is properly configured to work with the control panel The first initializing commands a...

Page 30: ...be changed to any sequence of 16 alphanumeric characters As long as it is set by default you can start the program with default code 1 2 3 4 by pressing the ENTER key no access code need to be entere...

Page 31: ...DLOAD10 DEFAULT SETTINGS Control panel configuration restore with FS107 function service code 12345 master code 1234 control panel password communication identifier 3175B9 computer password communica...

Page 32: ...all zones 480 ms output OUT1 audible signaling BURGLARY ALARM function operation time equal to global time polarity 12 V assigned to all zones output OUT2 visual signaling BURGLARY ALARM function ope...

Page 33: ...andby power supply recommended battery 12 V 7 Ah Battery charging current 350 mA Battery cut off voltage 10 5 V Battery cutout protection polymer fuse 2 5 A Operational temperature range 10 55 C Print...

Page 34: ...1x0 25 8 8 Ah AAv 1 25x 0 07x12 0 12x12 0 08x12 0 5x0 25 0 05x0 25 4 22 Ah Recommended standby power supply 12 V 7 5 Ah battery Assumed current consumption by a single detector 20 mA If the capacity...

Page 35: ...n telephone line public telephone line voice synthesizer see p 20 power supply outputs low current programmable outputs see p 19 programmable zones description of detectors connection see p 16 CTL inp...

Page 36: ...ed p 12 it requires a new cable now p 12 The schematic view of the CA 6 main board has been changed p 12 and 33 The figure of connection of the detectors to the control panel has been changes to a new...

Reviews: