Guard control function
The functioning of the guard control function consists in automatically checking that the, so-
called, guard code is entered on the keypad with a preset frequency. The entry of the code is
saved in the log event, and the lack of entering the guard code after a preset period of time
can be signaled on an output which has the proper function. These events can be reported to
the monitoring station.
To activate the function you must:
•
program the guard code – in the user function 2 (creating new user) a code with
authority level 5 (instead of the guard code, the user function 7 can also be used
- activation of the „switch MONO" output),
•
set a suitable timer to perform the function 7 – „partition monitoring” function (FS106),
•
program the timer control time (functions FS102, FS103, depending on the partition).
Telephone messaging – alarm reporting
The telephone messaging function requires that the following be programmed:
•
FS5 and FS131
– activate the “telephone messaging” option, set the “dialing system”
option as required by the telephone exchange,
•
FS87 to FS90
– enter at least one telephone number,
•
FS95
– define the partitions from which alarms are to be reported to the telephone
numbers programmed in functions FS87-90,
•
FS100
– number of telephone messaging rounds higher than zero and than number of
redials in a round,
Note
: You should also program in FS95 what kind of message will be sent – if no message
is selected for the pager, the CA-6 will use a voice message from the synthesizer.
When the above parameters are correctly programmed and the alarm is triggered, the
on-board LED (designated as „DIALER”) should go on, which indicates that the panel has
started telephone messaging (with pulse dialing the LED is blinking). It is recommended to
test the messaging. To this purpose, use the ordinary headset connected to the „telephone
line monitoring” jack in the SM-2 synthesizer (parallel connection of a telephone set to
„monitor” the communication will interfere with the messaging operation). The telephone
messaging will start immediately after triggering the alarm. Alarm clearing will interrupt the
telephone messaging.
Typical problems with starting the voice messaging:
•
control panel takes no attempts to call
– not all of the above mentioned options were
programmed;
•
control panel goes online, but dials no number
– no dial tone or a non-standard dial
tone from the telephone exchange – find out the cause of missing signal or deactivate the
dial tone test option in FS5 if the signal is non-standard;
•
control panel establishes connection, but sends no voice message
– wrongly
programmed FS95 – messaging to pager selected (not a voice message from the
synthesizer);
•
control panel establishes connection, sends a message too early or too late
– the
control panel recognizes answering the call on the basis of sound signals on the telephone
line. After the handset is lifted a 4 seconds delay in message sending is permissible – if
commutation signals on the telephone line are non-standard or there is strong interference
(clicks, noises), the panel may not function properly – then you can extend the message
by activating the “double message” option in FS5 or you can deactivate the call answer
recognition option;