Satel CA-6-P Installer Manual Download Page 25

CA-6 

SATEL 

 

23 

Guard control function 

The functioning of the guard control function consists in automatically checking that the, so-
called, guard code is entered on the keypad with a preset frequency. The entry of the code is 
saved in the log event, and the lack of entering the guard code after a preset period of time 
can be signaled on an output which has the proper function. These events can be reported to 
the monitoring station. 
To activate the function you must: 

  program  the  guard  code  –  in  the  user  function  2  (creating  new  user)  a  code  with 

authority  level  5  (instead  of  the  guard  code,  the  user  function  7  can  also  be  used 
- activation of the „switch MONO" output), 

  set a suitable timer to perform the function 7 – „partition monitoring” function (FS106), 

  program the timer control time (functions FS102, FS103, depending on the partition). 

Telephone messaging – alarm reporting  

The telephone messaging function requires that the following be programmed: 

 

FS5  and  FS131

  –  activate  the  “telephone  messaging”  option,  set  the  “dialing  system” 

option as required by the telephone exchange, 

 

FS87 to FS90 

– enter at least one telephone number,

 

 

 

FS95

  –  define  the  partitions  from  which  alarms  are  to  be  reported  to  the  telephone 

numbers programmed in functions FS87-90, 

 

FS100

  –  number  of  telephone  messaging  rounds  higher  than  zero  and  than  number  of 

redials in a round, 

Note

:  You should also program in FS95 what kind of message will be sent – if no message 

is selected for the pager, the CA-6 will use a voice message from the synthesizer. 

When  the  above  parameters  are  correctly  programmed  and  the  alarm  is  triggered,  the 
on-board  LED  (designated  as  „DIALER”)  should  go  on,  which  indicates  that  the  panel  has 
started  telephone  messaging  (with  pulse  dialing  the  LED  is  blinking).  It  is  recommended  to 
test  the  messaging.  To  this  purpose,  use  the  ordinary  headset  connected  to  the  „telephone 
line  monitoring”  jack  in  the  SM-2  synthesizer  (parallel  connection  of  a  telephone  set  to 
„monitor”  the  communication  will  interfere  with  the  messaging  operation).  The  telephone 
messaging  will  start  immediately  after  triggering  the  alarm.  Alarm  clearing  will  interrupt  the 
telephone messaging. 

Typical problems with starting the voice messaging: 

 

control  panel  takes  no  attempts  to  call 

–  not  all  of  the  above  mentioned  options  were 

programmed; 

 

control  panel  goes  online,  but  dials  no  number

  –  no  dial  tone  or  a non-standard  dial 

tone from the telephone exchange – find out the cause of missing signal or deactivate the 
dial tone test option in FS5 if the signal is non-standard; 

 

control  panel  establishes  connection,  but  sends  no  voice  message 

–  wrongly 

programmed  FS95  –  messaging  to  pager  selected  (not  a  voice  message  from  the 
synthesizer); 

 

control  panel  establishes  connection,  sends  a  message  too  early  or  too  late 

–  the 

control panel recognizes answering the call on the basis of sound signals on the telephone 
line.  After  the  handset  is  lifted  a  4  seconds  delay  in  message  sending  is  permissible  –  if 
commutation signals on the telephone line are non-standard or there is strong interference 
(clicks, noises), the panel may not function properly –  then you can extend  the message 
by  activating  the  “double  message”  option  in  FS5  or  you  can  deactivate  the  call  answer 
recognition option; 

Summary of Contents for CA-6-P

Page 1: ...Firmware Version 6 06 GDA SK ca6i_en 05 09 INSTALLER MANUAL...

Page 2: ...a fully discharged battery with voltage on unloaded terminals less than 11 V to the alarm panel In order to avoid equipment damage the fully discharged never used battery should be precharged by means...

Page 3: ...of Telephone Line 20 Connection of Voice Synthesizer 20 Connection of power supply 20 Starting the control panel 21 Entering service mode from pins 22 ACTIVATING SELECTED FUNCTIONS 22 Guard control f...

Page 4: ...s of telephone exchange signals which enables an alarm voice message to be sent after answering the call support of NOKTON radio messaging in PC16OUT format built in port RS 232 TTL the RJ socket is p...

Page 5: ...lation counters a zone violation code is sent to the station until the number of violations specified for that counter is exceeded programming in FS7 Then the violation triggers an alarm a zone alarm...

Page 6: ...olation of this zone during countdown of the exit delay will trigger an alarm Reaction time for each zone can be programmed within 0 016 s to 4 08 s For delayed zones an individual time delay can be s...

Page 7: ...larms the output starts on detecting any keypad alarm The output can remain active for a specified time from 01 to 99 seconds or from 01 to 99 minutes or until the alarm is cleared by the user During...

Page 8: ...mited to indicating the exit delay for specified partition 17 entry delay status the output is active during the entry delay countdown Operation of the output can be limited to selecting the entry del...

Page 9: ...med mode it functions similarly to the ARM STATUS output but it is activated right after exit delay starts not after changeover from the exit delay to the armed mode it can be used for example as indi...

Page 10: ...e one left by the deleted user Individual users may have the following authority levels 1 accessible all functions except creating and deleting users 2 accessible arming and disarming change of access...

Page 11: ...onnected to the station the control panel will suspend dialing the station number for 60 seconds and if the message is also to be transmitted by the dialer it will make the line available to the diale...

Page 12: ...top dialing the number for which connection cannot be established no answer permanently busy etc Messaging can be carried on until successful It is also possible to determine the maximum number of ret...

Page 13: ...e control panel Notification of the monitoring station will take place after communication with the computer is over 3 Establishing of communication from the control panel by calling the function 0 by...

Page 14: ...connected with a special cable manufactured by SATEL The cable includes a converter changing the signal into a standard corresponding to the RS 232 port in the computer 12 V 12 V The data can be tran...

Page 15: ...l system the stabilized voltage of the control panel power supply is 13 6 V to 13 8 V and is factory set battery status monitoring system with optional disconnection of the battery if discharged durin...

Page 16: ...n of the housing be careful so as not to damage the wires which will be passed through the hole in its back panel When the housing is secured you can install the control panel main board and proceed t...

Page 17: ...e inputs The keypad Z1 terminal is treated as zone 7 Z2 as zone 8 Provision is made for connecting additional keypads in parallel with the first one Each keypad should be connected to the control pane...

Page 18: ...nables the status of detector and its tamper contact to be monitored at the same time The detectors may be supplied from any of the electronically protected outputs OUT1 to OUT3 The output should be p...

Page 19: ...M 12V C TMP EOL NO 2 2k Fig 7 Example of connecting NO type detector in EOL configuration to control panel COM OUT3 DTA CLK CTL COM Z1 Z2 Z3 COM Z4 KPD COM CA 6 EOL NC 2 2k NC TMP COM 12V NC TMP Fig 8...

Page 20: ...T2 COM OUT3 COM 12 V LIMITER 2 2A LIMITER 2 2A LIMITER 2 2A LOAD LOAD LOAD KPD LIMITER 1 5A Fig 10 Connection of a load to high current outputs In the case of sirens which alarm after power is supplie...

Page 21: ...tter NEMROD system format PC16OUT In such a case it is necessary to change the operating mode of these outputs by activating a suitable option in the service function 5 During operation with the NOKTO...

Page 22: ...multicore cable This may result in damage to the system in case of a high voltage punch through from the telephone line Telephone terminals of the panel should be connected to PSTN analog lines only C...

Page 23: ...avoiding damage to the security system elements caused by possible installation faults Note Should it be necessary to completely disconnect the control panel power supply the mains and the battery re...

Page 24: ...he user passwords FS110 and or reset the event log FS108 Note Shorting the pins and power up alone will restore no parameters These operations will call up the service mode thus making it possible to...

Page 25: ...en the above parameters are correctly programmed and the alarm is triggered the on board LED designated as DIALER should go on which indicates that the panel has started telephone messaging with pulse...

Page 26: ...he list from the monitoring station operator the codes can be one digit the other character being 0 or two digit as required by the station the codes with inappropriate length may block communication...

Page 27: ...e transmission formats supported by the given station e g ambiguous names of the formats errors in the data entered into the control panel as well as poor quality of the telephone connections Often on...

Page 28: ...P mainboard Fig 14 Connecting control panel to modem for local mode programming Local communication connect the computer modem to the TIP and RING control panel terminals the telephone line must be di...

Page 29: ...s initialization error wrong command initializing the modem Correct initialization of the modem does not mean it is properly configured to work with the control panel The first initializing commands a...

Page 30: ...be changed to any sequence of 16 alphanumeric characters As long as it is set by default you can start the program with default code 1 2 3 4 by pressing the ENTER key no access code need to be entere...

Page 31: ...DLOAD10 DEFAULT SETTINGS Control panel configuration restore with FS107 function service code 12345 master code 1234 control panel password communication identifier 3175B9 computer password communica...

Page 32: ...all zones 480 ms output OUT1 audible signaling BURGLARY ALARM function operation time equal to global time polarity 12 V assigned to all zones output OUT2 visual signaling BURGLARY ALARM function ope...

Page 33: ...andby power supply recommended battery 12 V 7 Ah Battery charging current 350 mA Battery cut off voltage 10 5 V Battery cutout protection polymer fuse 2 5 A Operational temperature range 10 55 C Print...

Page 34: ...1x0 25 8 8 Ah AAv 1 25x 0 07x12 0 12x12 0 08x12 0 5x0 25 0 05x0 25 4 22 Ah Recommended standby power supply 12 V 7 5 Ah battery Assumed current consumption by a single detector 20 mA If the capacity...

Page 35: ...n telephone line public telephone line voice synthesizer see p 20 power supply outputs low current programmable outputs see p 19 programmable zones description of detectors connection see p 16 CTL inp...

Page 36: ...ed p 12 it requires a new cable now p 12 The schematic view of the CA 6 main board has been changed p 12 and 33 The figure of connection of the detectors to the control panel has been changes to a new...

Reviews: