background image

SATEL ASW-210 

Operating modes 

You can select the operating mode when configuring the ASW-210 controller settings (refer 
to the ABAX 2 controller / INTEGRA 128-WRL control panel manual). For each position 
occupied by the controller on the list of wireless devices, you can select a different operating 
mode: 

mode 0

  – the relay can only be controlled via the controller / control panel. The state of the 

wired input is of no consequence for the relay, but information about the input 
state is sent to the controller / control panel. 

mode 1

  – the relay can be controlled via the controller / control panel as well as by using the 

monostable switch connected to the wired input. Information about the input state 
is sent to the controller / control panel. 

mode 2

  – the relay can be controlled via the controller / control panel as well as by using the 

bistable switch connected to the wired input. Information about the input state is 
sent to the controller / control panel. 

4.  Installation 

Disconnect power before making any electrical connections. 

Connect the controller to a single-phase network according to the applicable 
standards. 

Do not remove the controller from the enclosure. Installing the controller 
without enclosure or with a damaged enclosure poses a risk of electric shock 
and may damage the module. 

The wired inputs of the controller are not galvanically isolated. 

It is not recommended to use the controller to switch the capacitive loads (e.g. 
LED lighting power supply units, LED lamps) more frequently than every 10 
seconds. 

Do not connect more than one LED lighting power supply to the relay output. 

The ASW-210 controller is designed for mounting inside an electrical junction box (60 mm 
deep). It should be installed indoors, in spaces with normal air humidity. When choosing the 
installation location, remember that thick masonry walls, metal partitions etc. reduce the radio 
signal range. 
The electrical circuit to which the controller is to be connected must be protected by 
a suitable safety device. Let the owner / user of the ABAX 2 / ABAX system know how to 
disconnect the device from the mains supply (e.g. indicate the fuse or circuit breaker 
protecting the controller supply circuit). 
To connect the wires, use screw terminal blocks, splicing connectors, etc. 
1.  Power off the circuit to which the controller is to be connected. 
2.  Open the electrical junction box in which the controller is to be installed. 
3.  Connect the controller to the 230 V AC supply circuit (brown wire [L] to phase wire; blue 

wire [N] to neutral wire – Fig. 2). 

4.  Place the controller in the junction box. Make sure the electric wires are behind the 

controller enclosure. 

5.  Power on the circuit to which the controller is connected. 

Summary of Contents for ASW-210

Page 1: ...ASW 210 Flush mounted wireless two channel 230 V AC controller Firmware version 1 00 asw 210_en 07 19 SATEL sp z o o ul Budowlanych 66 80 298 Gdańsk POLAND tel 48 58 320 94 00 www satel eu ...

Page 2: ...e of the device is located on the enclosure base SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and software Current information about the changes being introduced is available on our website Please visit us at http www satel eu Hereby SATEL sp z o o declares that the radio equipment type ASW 210 is in compliance with Dir...

Page 3: ... the controller outputs 2 programmable wired inputs support for NO or NC type switches Encrypted two way radio communication in the 868 MHz frequency band AES standard for the ABAX 2 system Transmission channel diversity 4 channels for automatic selection of the one that will enable transmission without interference with other signals in the 868 MHz frequency band ABAX 2 system only Remote update ...

Page 4: ...hase wire NO1 gray NO contact of the relay output 1 normally it is disconnected from the common contact C does not conduct electricity NO2 black NO contact of the relay output 2 normally it is disconnected from the common contact C does not conduct electricity C red common contact C of the relay outputs Terminals SW1 SW2 control input NO N for connecting 230 V AC supply neutral wire Radio communic...

Page 5: ...a risk of electric shock and may damage the module The wired inputs of the controller are not galvanically isolated It is not recommended to use the controller to switch the capacitive loads e g LED lighting power supply units LED lamps more frequently than every 10 seconds Do not connect more than one LED lighting power supply to the relay output The ASW 210 controller is designed for mounting in...

Page 6: ...e ASW 210 controller and check if it improves the signal strength The controller can be installed in the selected junction box if the signal strength is higher than 40 9 Power off the circuit to which the controller is connected 10 Open the junction box and remove the controller 11 Connect the wires of controller relay outputs to the wires of electrical circuits to be controlled by the controller ...

Page 7: ...SATEL ASW 210 5 ...