background image

APS-15 SATEL 

 

3

4.  Using the installed cables, connect the transformer output voltage (rated at 18V AC) to 

the AC terminals on the electronics board.  

5.  Connect the cables of receivers to the ter12V and COM of the terminal block on 

power supply board. 

6.  If necessary, connect the AWS and AWB outputs with the control panel zones. During 

normal operation of the power supply unit, the signaling output is shorted to the ground 
(0V), but when a failure situation occurs, it becomes cut off from the common ground.  

10k

3.9k

10R

AWS

BC 847B

10k

3.9k

10R

AWA

BC 847B

AWS

AWA

 

Fig. 2. Diagrams of AWS, AWA outputs 

7.  Using jumpers, set the time delay on the AC FAIL DELAY pins after which 230V mains 

supply failure will be signaled on the AWS output. The possible settings are: 

 0 

seconds 

–   

 

 Pins 

open 

 60 

seconds 

–   

 

 Pins 

shorted 

 600 

seconds 

– 

 

 

 1800 

seconds 

– 

 

 

8. Using the BEEP pins, determine, whether the beeper is to be switched on (jumper on), or 

not (jumper off). 

9.  Switch on the 230V AC mains supply and insert the mains fuse located in the transformer 

housing (if all connections are made correctly, LEDs MAINS and BATTERY should light 
up). 

10. Having connected the power supply unit, you can measure the voltage across battery 

cables. The voltage set during production process is 13.6 – 13.8V and should not be 
changed.  

11. Connect the battery according to the colour marking. 

If the battery is discharged, the green LED (BATTERY) will start blinking approx. 
4 minutes after the 230V AC mains supply is switched on. If the battery is connected after 
this time (green LED is blinking), the battery charging conditions will be known when the 
next test is carried out by the power supply after approx. 12 minutes. During the testing, 
the processor reduces power supply voltage down to about 10.5V, while the receivers 
are supplied from the battery 

The battery state of charge is tested every 4 minutes for some 10 to 20 seconds. If the 
battery voltage decreases to approx. 11V over three consecutive cycles, the power 
supply unit will signal a failure, and when the voltage drops to 9.5V, the power supply will 
disconnect the battery to protect it from complete discharge and damage. 

The battery test function can be disabled by removing the jumper TEST BAT. Disabling 
the test will also deactivate the battery failure signaling on the AWA output, without, 
however, switching off the circuit which protects the battery from complete discharge. 

12. Next, the proper operation of failure monitoring circuits can be checked (with the TEST 

BAT jumper set on):  