background image

 SATEL 

APS-15 

 

4

turn off  AC mains supply - the red LED (MAINS) shall start blinking and the power 
supply will start audibly signaling a failure. After the time set on pins, the AWS output 
status shall change. When the mains power is restored, the LED will light permanently, 
the audible signaling shall be disabled, and after the time delay set on pins, the AWS 
output shall stop signalling 

disconnect the battery – after approx. 12 minutes, the green LED (BATTERY) will start 
blinking and the power supply will start audibly signalling a failure. The failure status will 
occur on the AWA output. The reconnection of the battery will clear the visual (LED) and 
the audible (buzzer) alarm in approx. 12 minutes. 

After installing and checking the proper operation of the power supply, its housing can be 
closed.  

As the power supply has no isolating switch to disconnect the mains 
supply, it is important to inform the user or the owner of this device about 
the way of disconnecting it from the mains (e.g. by indicating the fuse 
which protects the supply circuit).

 

2. Technical data 

Power supply type................................................................................................................... A 

Transformer power voltage ..........................................................................................AC 230V 

Electronics board supply voltage (from transformer)...............................................17...20V AC 

Rated output voltage ........................................................................................ 13,6...13,8V DC 

Effective current ................................................................................................................. 1,5A 

Battery charging current.....................................................................................approx. 500mA 

Recommended battery............................................................................................... 12V / 7Ah 

Ampacity of AWS output (OC type)..........................................................................max. 50mA 

Ampacity of AWA output (OC type)..........................................................................max. 50mA 

Operating temperature range (class I) ......................................................................+5...+40°C 

Electronics board dimensions .................................................................................. 102x76mm 

Housing dimensions......................................................................................... 170x270x81mm 

Weight (without battery) .................................................................................................... 2,0kg 

 

The latest EC declaration of conformity and certificates are available for 

downloading on

 

website www.satel.pl 

 

 

 

SATEL sp. z o.o. 

ul. Schuberta 79 

80-

172 Gda

ń

sk

 

POLAND 

tel. + 48 58 320 94 00 

[email protected] 

www.satel.pl

 

Reviews: