SATEL
APS-15
4
turn off AC mains supply - the red LED (MAINS) shall start blinking and the power
supply will start audibly signaling a failure. After the time set on pins, the AWS output
status shall change. When the mains power is restored, the LED will light permanently,
the audible signaling shall be disabled, and after the time delay set on pins, the AWS
output shall stop signalling
disconnect the battery – after approx. 12 minutes, the green LED (BATTERY) will start
blinking and the power supply will start audibly signalling a failure. The failure status will
occur on the AWA output. The reconnection of the battery will clear the visual (LED) and
the audible (buzzer) alarm in approx. 12 minutes.
After installing and checking the proper operation of the power supply, its housing can be
closed.
As the power supply has no isolating switch to disconnect the mains
supply, it is important to inform the user or the owner of this device about
the way of disconnecting it from the mains (e.g. by indicating the fuse
which protects the supply circuit).
2. Technical data
Power supply type................................................................................................................... A
Transformer power voltage ..........................................................................................AC 230V
Electronics board supply voltage (from transformer)...............................................17...20V AC
Rated output voltage ........................................................................................ 13,6...13,8V DC
Effective current ................................................................................................................. 1,5A
Battery charging current.....................................................................................approx. 500mA
Recommended battery............................................................................................... 12V / 7Ah
Ampacity of AWS output (OC type)..........................................................................max. 50mA
Ampacity of AWA output (OC type)..........................................................................max. 50mA
Operating temperature range (class I) ......................................................................+5...+40°C
Electronics board dimensions .................................................................................. 102x76mm
Housing dimensions......................................................................................... 170x270x81mm
Weight (without battery) .................................................................................................... 2,0kg
The latest EC declaration of conformity and certificates are available for
downloading on
website www.satel.pl
SATEL sp. z o.o.
ul. Schuberta 79
80-
172 Gda
ń
sk
POLAND
tel. + 48 58 320 94 00
www.satel.pl