Appendix B Programmable Parameters
139
Table B-7 Setpoint Trigger Parameters
Group
Parameter
Unit
Range
À
Condition
label
Label
Name
Á
label
ti
Π
E
Time
00.00.00 to
23.59.59
dAY.U
Day of week
YEAr
Year
0 to 99
Π
on
Month
1 to 12
dAY.
Π
Day of month
1 to 31
hour
Hour
0 to 23
Π
in
Minute
0 to 59
SEC
Second
0 to 59
rt.Ph
Real-time values per phase
GE/LE/Eq/nE
U 1
Voltage L1/L12
V
0 to Vmax
U 2
Voltage L2/L23
V
0 to Vmax
U 3
Voltage L3/L31
V
0 to Vmax
cur1
Current L1
A
0 to Imax
cur2
Current L2
A
0 to Imax
cur3
Current L3
A
0 to Imax
Ac.P1
kW L1
kW
-Pmax to Pmax
Ac.P2
kW L2
kW
-Pmax to Pmax
Ac.P3
kW L3
kW
-Pmax to Pmax
rE.P1
kvar L1
kvar
-Pmax to Pmax
rE.P2
kvar L2
kvar
-Pmax to Pmax
rE.P3
kvar L3
kvar
-Pmax to Pmax
AP.P1
kVA L1
kVA
0 to Pmax
AP.P2
kVA L2
kVA
0 to Pmax
AP.P3
kVA L3
kVA
0 to Pmax
PF1
Power factor L1
-1.00 to 1.00
PF2
Power factor L2
-1.00 to 1.00
PF3
Power factor L3
-1.00 to 1.00
th.U1
Voltage THD L1/L12
%
0 to 100.0
th.U2
Voltage THD L2/L23
%
0 to 100.0
th.U3
Voltage THD L3
%
0 to 100.0
th.C1
Current THD L1
%
0 to 100.0
th.C2
Current THD L2
%
0 to 100.0