![Satec PM295 Installation And Operation Manual Download Page 118](http://html1.mh-extra.com/html/satec/pm295/pm295_installation-and-operation-manual_1200390118.webp)
110
Technical Specifications
Measurement Specifications
Parameter, unit
Full scale
Accuracy, %
Range
Resolution @ range
Rdg
FS
Conditions
Front panel display
Comm.
Voltage, V
120V
×
PT
@ 120V
380V
×
PT
@ 660V
208V
×
PT
@ 120V
660V
×
PT
@ 660V
0.2
10% to 120%
FS
0 to 999,000
1 V
@ 1 to 999 V
≤
1%
@ 1,000 to 999,000 V
1 V
Line current, A
CT primary current
0.2
2% to 120%
FS
0 to 60,000
1 A
@ 1 to 9,999 A
≤
0.1% @
10,000 to 60,000A
1 A
Active power, kW
0.36
×
PT
×
CT
@ 120V input
1.14
×
PT
×
CT
@ 660V input
0.5
|PF|
≥
0.5
•
0 to
±
2,147,000
1 kW
@ 1 to 99,999/-9.999
≤
0.01%
@ 100 to 2,147 MW
≤
0.1%
@ -10 to -2,147 MW
1 kW
Reactive power,
kvar
0.36
×
PT
×
CT
@ 120V input
1.14
×
PT
×
CT
@ 660V input
0.5
|PF|
≤
0.9
•
0 to
±
2,147,000
1 kvar
@ 1 to 99,999/-9.999
≤
0.01%
@100 to 2,147Mvar
≤
0.1%
@ -10 to -2,147 Mvar
1 kvar
Apparent power,
kVA
0.36
×
PT
×
CT
@ 120V input
1.14
×
PT
×
CT
@ 660V input
0.5
|PF|
≥
0.5
•
0 to 2,147,000 1 kVA
@ 1 to 9,999
≤
0.1%
@ 10 to 2,147 MVA
1 kVA
Power factor
1
1
|PF|
≥
0.5
-0.99 to +1.00 0.01
0.01
Neutral current, A
CT primary current
0.5
2% to 120%
FS
0 to 60,000
1 A
@ 1 to 999 A
≤
1%
@ 1,000 to 60,000 A
1A
Auxiliary current,
mA/A
Auxiliary CT primary
current
1
2% to 120%
FS
0 to 60,000
1 mA/A
@ 1 to 999 mA/A
≤
1%
@ 1,000 to 60,000
1 mA/A
For Ln reading
and for
3OP2/3OP3
wiring
modes
For LL reading
except
3OP2/3OP3
wiring modes
or
or