14
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
record,
1-65534 – device response code
exception code (See 2.3-2.4)
+2,3
Record time, seconds since 1/1/1970
F1
sec
UINT32
R
+4,5
Record sequence number
0-65535
UINT32
R
+6 Data
register
0-65535
UINT16
R
...
+119 Data
register
0-65535
UINT16
R
Event Log Transfer Blocks
10016-10031
File Request Block
+0
Function
3 = set file position
5 = reset file position
11 = read file
UINT16
R/W
3 - changes the file position
5 - sets the file position at the first
(oldest) record
11 - opens the file for reading from
the present file position
+1
Record sequence number (with functions 3, 11)
0-65535
UINT16
R/W
The record sequence number with
function 11 does not change the file
position
+2-12 Reserved
+13
First (oldest) record sequence number
UINT16
R
+14
Next sequence number to be used
UINT16
R
+15 Reserved
10000-10009
File Transfer Block
+0,1
Event log status
0 - no new events, 1 – data is valid,
-1 – current record corrupted
UINT32
R
+2,3
Event sequence number
0-65535
UINT32
R
+4,5
Event type ID
F2
UINT32
R
+6,7 Device
ID
0-247
UINT32
R
+8,9
Event time, seconds since 1/1/1970
F1
sec
UINT32
R
+10,11 Event
data
F3
UINT32
R
4.2 Digital Inputs
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
Digital Inputs
12544
Digital inputs DI1-DI4
0x0000 - 0x000F
UINT16
R
The digital input register returns the state of the level-sensitive digital inputs in a 16-bit packed format.