background image

Set Application
Number

Fig.5

Set IAC
Address

Fig.6

REMOTE OPERATION AND INTERROGATION

The IAC is connected, as part of a network, to a remote computer via
the Serial Link, all of the setting and interrogation functions are
carried out at the computer terminal.
Each IAC will be identified by a unique Address Code which is set up
via switch SW1 located to the right of the upper terminal block.  This
allows the computer to select the desired IAC on the network.  Up to
a maximum of 32 IAC Controllers (or similar compatible devices) may
be connected to a LAN (more if a separate MIU or IAC Touch-screen
is used).

TOUCH-SCREEN SUB LAN ADDRESS

If the IAC is on a Touch-screen Sub LAN then the address which the
computer uses is as follows:-
( (Touch-screen address – 64) x 100) + IAC set address

e.g. Touch-screen address = 68

IAC address = 3
Computer address for the IAC = ( (68 – 64) x 100) +3 = 403

In this way it is possible for large sites to have a unique address for
every network controller.

SETTING THE TOUCH-SCREEN ADDRESS

To set the Touch-screen address and Baud rate see the
Touch-screen User Guide.

SETTING THE ADDRESS, BAUD RATE AND
APPLICATION OF THE IAC 600 BASE UNIT

Instructions 1 to 4 will COLD START your IAC and clear out the
memory.
1. Ensure all IAC outputs are disconnected from the plant.
2. Set bit switch 1 "ON".  Set all other bit switches to "OFF" - see fig.

5.

3. Set bit switch 8 to "ON" and then back to "OFF", this will load

preset 1.

4. Set all bit switches to "OFF".  Set bit switch 8 to "ON" and then

back to "OFF", this will load preset 0.

5. If you are using preset 0 you should now set the controller

address.  If you are using a hardware preset application set the
application number on bit switches 1 to 6 and ensure that bit
switch 7 is set to "OFF".

6. If the IAC is not to be connected to a computer then it is not

necessary to set an address for it.

7. Once the Application Number is set it must be entered into the

IAC by ‘cold starting’ the controller.  This is achieved by setting bit
switch 8 to "ON" and then setting bit switch 8 back to "OFF".

SW1

SWITCH

(Increment No.)

POSITION

Off/

Open/0

On/

Closed/1

1
2
3
4
5
6

0
0
0
0
0
0

1
2
4
8

16
32

7

8

Set Appli-

cation

Run

Set

Address

Cold Start

Example:
Switch settings as shown in Fig. 5.

Switch

Represents

1

1     

2

0     

3

4     

4

0     

5

0     

6

0     

TOTAL

=

5   

7

8

Application Number

Run

Set Application

On/Closed/I
Off/Open/0

OPEN

Switch

SW1

SWITCH

(Increment No.)

POSITION

Off/

Open/0

On/

Closed/1

1
2
3
4
5
6

0
0
0
0
0
0

1
2
4
8

16
32

7

8

Set Appli-

cation

Run

Set

Address

Cold Start

Switch

Represents

1

1     

2

0     

3

4     

4

0     

5

0     

6

32   

TOTAL

=

37   

7

8

Address

Run

Set Address

On/Closed/I
Off/Open/0

OPEN

Switch

8. Set the controller address on bit switches 1 to 6 and set bit switch

7 to "ON".  See fig.6.

9. Once the address has been set it must be entered into the IAC by

‘cold starting’ the controller.  This is achieved by setting bit switch
8 to "ON" and then setting bit switch 8 back to "OFF".

Example:
Switch settings as shown in Fig. 6.

10. The IAC application and address has now been set up, the Baud

rate is automatically set to 1200 Baud (this is done whenever the
controller is cold started).

Notes:
1. Do not set more than one network device to the same address.
2. If a sub-LAN is used then addresses 1 to 31 can NOT be used on

the main LAN.

3. Protocol and wiring information for OEM communications

programmes are available from Marketing Department, Slough
Office.

4. The IAC operates at 1200 Baud.

05/98

19 - 24

DS 2.951A

Summary of Contents for IAC 600

Page 1: ...e Switch Module 3 Analogue Averaging Module 4 Comparator Module 4 Limiter Module 4 Look up Table Module 4 Scaling Module 4 Threshold Module 4 Rate Limiting Module 4 LOGIC MODULES NOT Module 5 AND Module 5 XOR Module 5 Latch Module 5 Delay Module 5 Rotation Module 6 Stopwatch Module 6 Counter Module 6 CONTROL MODULES Controller Module 6 Optimiser Module 8 Enthalpy Comparator Module 9 Pulse Pair Dri...

Page 2: ...ned The screen should be earthed only at the IAC controller using one of the earth terminals supplied DO NOT USE AN ISOLATED GROUND 6 Ensure that the serial link connections are screened LAN A and LAN B screens must be connected to a verified good earth ONLY at the computer MIU LAN A and LAN B screens should be connected to the IAC isolated ground terminals of each IAC on the LAN DO NOT USE THE IA...

Page 3: ... parameter selects the units that can be used for the input C F Ohms or Lux C ANALOGUE INPUT MODULES VOLTAGE x 6 Current Measured Value as a percentage of 10 Volts review only 0 to 100 DIGITAL TRIAC OUTPUT MODULES x 8 Output State review only On or Off Override State None On or Off None ANALOGUE OUTPUT MODULES x 4 Current Output Value as a percentage of 10 Volts review only 0 to 100 Override Value...

Page 4: ...le to function correctly 10 000 to 10 000 IN OUT 0 0 10 2 20 3 30 4 40 6 50 10 60 16 70 25 80 40 90 63 100 100 SCALING MODULE x 8 The Scaling module is used to re scale an analogue signal based on minimum and maximum input and output values From these values the IAC scales all the points in between linearly For example for values of 0 in 0 out and 50 in 100 out a 0 to 5 Volt input is expanded to a...

Page 5: ...g a NOT Gate after an AND Gate the output is inverted thus providing a NAND gate equivalent A NOR gate is created by connecting two or more inputs into a NOT gate By placing a NOT Gate after an XOR Gate an EQUIV Gate is created if both inputs are the same then the output is on if not the output is OFF LATCH MODULES x 8 The Latch module is used to take a momentary Digital input and give a latched o...

Page 6: ...so allows the user to set an initial count value if required 0 to 10 000 0 Rollover Count At a preset rollover count the module will give a momentary output from the primary output reset to zero and start counting again 0 to 10 000 1000 Count Rising and Falling Edges Sets the module to count both the rising and falling edges of the pulsed input Yes or No No CONTROL MODULES CONTROLLER MODULE 2 STAG...

Page 7: ...0 Stage 1 Integral Action Time 0 Off This parameter is the set time interval necessary for integral action time to increase the Stage 1 output by the current proportional level Set to 0 for purely proportional control 0 to 10 000 Seconds 300 Secs Stage 1 Derivative Action Time 0 Off This is usually left at zero It is used where a faster control action is required and reducing the Proportional Band...

Page 8: ... is having on the currently active stage As boost overrides the stage fully on On or Off OPTIMISER MODULE x 2 The optimiser module is self learning with optimum on and off selectable linear or BRESTART logarithmic optimisation and histogram display The optimiser can also be selected for heating or cooling plant operation The module has its own time schedule to set the occupancy times Inputs to the...

Page 9: ...Monday to Friday 0800 1700 Saturday to Sunday 0000 0000 Clear Histogram This is used to clear the histogram data if required Yes or No No Occupancy Setpoint This is the setpoint to be used by the optimiser 10 000 to 10 000 19 NOTE If the remote setpoint input is used then that will override the Occupancy Setpoint Optimiser Direction This sets the optimiser to operate a heating or cooling plant Hea...

Page 10: ...p 0 to 10 000 10 Step 2 Switch on Point This parameter is used to set the switch on point for the step 0 to 10 000 20 Step 3 Switch on Point This parameter is used to set the switch on point for the step 0 to 10 000 40 Step 4 Switch on Point This parameter is used to set the switch on point for the step 0 to 10 000 60 Step 5 Switch on Point This parameter is used to set the switch on point for the...

Page 11: ...t as 0300 If only one ON OFF is required for a day then the First ON time is set and also the First OFF The Second ON and second OFF should be set to the same time as the First OFF If the IAC is to be off all day set both ONs and OFFs to 0000 0000 to 2359 0800 1700 1700 1700 ALARM MODULES x 12 The Alarm module is used to monitor a digital signal when the signal is on the alarm module registers an ...

Page 12: ...to Null Output Mode reload defaults should be used to clear it This will overwrite any parameters set by the user Detector Sequence This setting selects the sequence in which the detectors are read The default setting is 0 and this setting gives an equal priority to all detectors Selecting 1 will give priority to temperature resistive input 1 and 2 gives priority to analogue Voltage input 1 Sequen...

Page 13: ...ule gives a pulsed digital output the rate of which can be set by the user As the rate is arbitrary and will vary with the controller workload it should be used for non critical applications only Flash Rate The flash rate is set in arbitrary units 0 being the fastest and 100 the slowest The on and off times are of similar length 0 to 100 5 DIGITAL ONE MODULE x 1 The module may be placed on screen ...

Page 14: ... a system but if the supplied application suits your system it may be used as it stands Hardware Preset Applications There are currently 4 preset applications that can be selected from the 8 way bit switch and they are as follows Preset 0 Fully configurable No links are made between modules This preset should be chosen if you wish to configure the IAC completely APPLICATION NOTES 1 If an applicati...

Page 15: ...HWS loops The time re synchronization input will re synchronize the IAC time to midnight Monday COMPENSATOR Schedule OUTSIDE SUPPLY 0 80 10 50 20 20 The outside temperature value is fed into a look up table The result is passed to the controller RPW input and is used to set the controller set value Proportional Band 10 Integral Action 300 Derivative Action 0 Ramp Time 60 Sample Time 10 HWS The HWS...

Page 16: ...chronization input will re synchronize the IAC time to midnight Monday COMPENSATOR Schedule OUTSIDE SUPPLY 0 80 10 50 20 20 The outside temperature value is fed into a look up table The result is passed to the controller RPW input and is used to set the controller set value Proportional Band 10 Integral Action 300 Derivative Action 0 Ramp Time 60 Sample Time 10 BOILER BACKEND VALVE The lead boiler...

Page 17: ...e time re synchronization input will re synchronize the IAC time to midnight Monday COMPENSATOR Schedule OUTSIDE SUPPLY 0 80 10 50 20 20 The outside temperature value is fed into a look up table The result is passed to the controller RPW input and is used to set the controller set value Proportional Band 10 Integral Action 300 Derivative Action 0 Ramp Time 60 Sample Time 10 BOILER BACKEND VALVE Th...

Page 18: ...ply and extract fans are speed controlled from the velocity sensors their set values being determined by the heating and cooling control demand signals The main temperature loop operates a heater battery and common cooler battery The dampers are modulated from the heating and cooling control demand signals and have a minimum fresh air setting of 30 In the event of the smoke switch activating the r...

Page 19: ... using a hardware preset application set the application number on bit switches 1 to 6 and ensure that bit switch 7 is set to OFF 6 If the IAC is not to be connected to a computer then it is not necessary to set an address for it 7 Once the Application Number is set it must be entered into the IAC by cold starting the controller This is achieved by setting bit switch 8 to ON and then setting bit s...

Page 20: ...ttom single height contains 34 to 41 and all of the Ground and Isolated Ground terminals Terminal numbers run from left to right 6 Ensure Terminal 2 is earthed 66The 24Vac Supply must have a 2A fuse The transformer must conform to EN 60742 DS 25 00 25 001 LAN A and LAN B should be screened with the screen earthed only on a verified good earth at the computer or MIU LAN A and B screens should be co...

Page 21: ...LAN addresses The number of IAC controllers on a Touch screen Sub LAN is limited to a maximum of 31 base units including the one the Touch screen is plugged into Each Touch screen can display up to 256 parameters ISOLATED GROUND ISOLATED GROUND LAN A and LAN B should be screened with the screen earthed only on a verified good earth at the computer or MIU 6LAN A and B screens should be connected to...

Page 22: ...from it 230Vac 45cm min 415Vac 58cm min both Voltages are with respect to earth and a maximum current of 15A For other Voltages currents refer to the IEE report titled Electro Magnetic Interference September 1987 ISBN85296353X WIRING PRECAUTIONS Wiring from IAC controller to Maximum length for 1 5mm2 core unscreened cable Maximum resistance per conductor Sensors DRT adjustable DRT non adjustable D...

Page 23: ...05 98 23 24 DS 2 951A ...

Page 24: ...n power supply until commissioning procedures have been carried out see page 2 Observe wiring precautions on page 22 Do not exceed maximum ambient temperature Interference with parts under sealed covers invalidates guarantee Design and performance of Satchwell equipment are subject to continual improvement and therefore liable to alteration without notice Information is given for guidance only and...

Reviews: