12
.
Temperature recalibration option
Parameter options:(-4~+4)
Factory default:0
13
.
℉
or
℃
readout option
Parameter options:(
℉
,
℃
)
Factory default:
℉
14
.
Program option
Parameter options:(7,0)
7: 7-day program function for the thermostat 0: non-program function for the thermostat
Factory default:7
This option apply only to HP2 or 2H setting in system type option
15
.
Sceond stage heating rate option
Parameter options:(FA,SL)
FA: Fast second stage heating rate. Second stage heating will activate 1.5
℉
below first stage heating
SL:Slow second stage heating rate. Second stage heating will activate 2.5
℉
below first stage heating
Factory default:7
16
.
Sceond stage cooling rate option
Parameter options:(FA,SL)
FA: Fast second stage cooling rate. Second stage cooling will activate 1.5
℉
above first stage
cooling
SL: Slow second stage cooling rate. Second stage heating will activate 2.5
℉
above first stage
cooling
Factory default:FA
17
.
Filter replacement run time option
Parameter options:(00-12)
This is a reminder to change or clean your air filter. This time can be set from 0 to 12 months in
1 month increments.
Factory default:00
1.The thermostat will display the “
Chg Filter
” after a set time of operation.
2.Selection of 00 will cancel the function.
This option apply only to HP2 or 2H setting in system type option
35
36