3287 DoorPosi-
tion Switch
12 Conductor
ElectroLynx Harness
From McKinney
H1 Harmony
Series
QC12 Electric
Hinge From
McKinney
READER NEG - Black, 1
READER POS - Red, 2
DATA 1 - White, 3
DATA 0 - Green, 4
RX (NO/NC) - Orange, 5
RX (COM) - Blue, 6
*EGND- Brown, 7
LED - Yellow, 8
LOCK NEG - Violet, 9
LOCK POS - Gray, 10
120 VAC
Input
Not Used
H N
G12/24VDC
- +
(-)
(+)
12VDC
DATA 1
DATA 0
RX
RX
DPS
UL294 Listed EAC Panel
Use (NC) for
DPS
Fail Safe
Operation
(NO) Fail
Secure
Operation
Lock Relay
**To prevent inductive “kickback” on solenoid-operated lockset, use of
‘flyback’ diode is required (1N4001, 1N5400 suggested)
Harmony Series H1 Cylindrical Lock
Typical Harmony Cylindrical Application Diagram (12/24VDC Lock)
MODE 1: RED LED ‘ON’ WHEN POWERED
Standard Application Shown - For Alternative Applications Contact 1-800-810-WIRE (9473)
12VDC System
• Reader Draw = 150mA
• 12VDC Solenoid Draw = 500mA
• Total System Draw = 650mA
24VDC System
• Reader Draw = 150mA (reader always 12VDC)
• 24VDC Solenoid Draw = 250mA
• Total System Draw = 400mA
*IMPORTANT: Pin 7 must be tied to earth ground in the access control panel.
Failure to follow proper ESD safe grounding procedures could lead to equipment failure.
5
A7884E • 800-810-WIRE (9473) • www.sargentlock.com
Lockbody
Power Supply
(By Others)
Electronic
Access
Control
Panel
(By Others)
ULC-S319 compliance:
EAC power supply utilizing battery backup
(30 minutes operation) is required.
Reader Electronics
Require 12 or 24VDC UL294 Listed,
Power Limited Power Supply (or UL603)
Reader Electronics Require 12 or 24VDC UL294 Listed, Power Limited Power Supply (or UL603)