SM830035
– 95 –
4
4. Service procedures
4. Service procedures
4-2
Checking the Electrical Components
(1)
Measurement of Insulation
Resistance
• The insulation is in good condition if the
resistance exceeds 1 M
Ω
.
1
Power Supply Wires
Clamp the earthed wire of the Power Supply
wires with a lead clip of the insulation resis-
tance tester and measure the resistance by
placing a probe on either of the power wires.
(Fig. 39)
Then measure the resistance between the earthed
wire and the other power wire. (Fig. 39)
2
Indoor Unit
Clamp an aluminum plate fin or copper tube
with the lead clip of the insulation resistance
tester and measure the resistance by placing
a probe on high voltage terminal on the
terminal plate (Fig. 40)
See Fig. 28.
3
Outdoor Unit (SPW-C253GH5)
Clamp a metallic part of the unit with the lead
clip of the insulation resistance tester and
measure the resistance by placing a probe on
1
and then
2
on the 8 or 6P terminal plate.
(Fig. 40)
See Fig. 28.
3
Outdoor Unit (SPW-C253GH8,
SPW-C363GH8, SPW-C483GH8)
Clamp a metallic part of the unit with the lead
clip of the insulation resistance tester and
measure the resistance by placing a probe on
5
and then
6
, and then
7
on the 8P terminal
plate. (Fig. 40)
See Fig. 29.
Fig. 39
Fig. 40
Copper
tube or
metallic part
Clip
Insulation
tester
Probe
Terminal plate
0639_X_S
Earthed wire
Clip
Probe
Insulation
tester
0638_X_S