<Combinations of Connectable Indoor Units>
The combinations of the indoor units listed in Table 1-a on page 2, Table 1-b on page 3, and Table 1-c on page 4 are
combinations solely of those units which can be operated concurrently. In addition to the combinations listed in the table,
other combinations of indoor units are possible provided that the following conditions are satisfied.
Conditions:
1.
At least two or more indoor units must be connected to the multi outdoor unit. It is not acceptable for only one indoor
unit to be connected.
2.
The total rated cooling capacity of the indoor units to be connected must be less than or equal to 200% of the rated
cooling capacity of the outdoor unit.
Example: When five indoor units are connected
If the following holds true
• Rated cooling capacity of SAP-CMRV3656EH outdoor unit: C=10 (kW)
• Rated cooling capacity of indoor units: K1, K2, ... (kW)
Then:
It is therefore possible to connect five units with respective capacities of 2.2 + 2.65 + 3.5 + 3.5 + 5.15. However, since this
combination is not found in the 5-room operation column of Table 1-c, operating all these units concurrently may result in
trouble. At a time like this, shut down at least one of the five indoor units to match one of the combinations found in the
4-room operation column of Table 1-b.
5-Room Outdoor Unit Combination Table
In this case, all the indoor units installed must not be operated concurrently under any
circumstances. Otherwise, the air conditioner may not run properly and trouble may
occur.
Be sure to operate the air conditioning system only when 2 or more
indoor units have been installed. If operated with only a single unit
installed, the returning fluid to the compressor may cause a malfunction.
CAUTION
C x 2 (200%) K1 + K2 + .......
10 x 2 2.2 + 2.65 + 3.5 + 3.5 + 5.15
20 17
NOTE
Save this Combination Table!
Please be sure to hand over this sheet to the user.