26
10-2-3. Only outdoor unit does not run.
A. Check setting temperature.
B. Check power relay in outdoor unit.
OK
NO
Is room temperature too low ?
Try to lower setting temperature by
temperature setting button cooler.
Outdoor unit still does
not run.
Remote control unit is defective.
• Try to run using another remote
control unit.
OK
• Measure coil resistance of power
relay.
Check indoor PCB Ass'y.
(PRA, PRB)