3
2-2. Major Component Specifications
2-2-1. Indoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No.
CB–K92GJ
Controls
Microprocessor
Control circuit fuse
250 V – 3.15 A
Remote Control Unit
RCS–3S4E–G
Type
Cross–flow
Number ... Dia. and length
mm
1 ... ø95 / L578
Fan motor model ... Number
IBH-884-020 ... 1
No. of poles ...rpm (High)
2 ... 1,290
Nominal output
W
20
Coil resistance (Ambient temp. 20°C)
Ω
WHT – BRN : 201
WHT – VLT : 261
Safety Type
Thermal
fuse
devices
Operating temp.
Open
°C
130
Close
—
Run capacitor
µF
1.5
VAC
440
Type
Stepping motor
Model
MP24GA3
Rating
DC 12 V
Coil resistance (Ambient temp. 25°C)
Ω
A pair of each terminal: 380 ± 7%
Coil
Aluminum plate fin / Copper tube
Rows
2
Fin pitch
mm
1.4
Face area
m2
0.110
Heat
Exch. Coil
Flap Motor
Fan & Fan Motor
Controller
PCB
Indoor Unit
SAP – K92A