33
6. ELECTRICAL DATA
6-1. Electrical Characteristics
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220V ~ 60Hz
Rating Conditions
Running Amps.
A
0.40
0.54
7.17
8.1
Power Input
kW
0.079
0.119
1.572
1.77
Full Load Conditions Running Amps.
A
0.40
0.54
8.87
9.8
Power Input
kW
0.079
0.119
1.942
2.14
Rating Conditions
: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit
SAP – K161GJA
Outdoor Unit
SAP – C161JA
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 – 240V ~ 50Hz
Rating Conditions
Running Amps.
A
0.37
/
0.38
0.48
/
0.50
6.35
/
6.42
7.2
/
7.3
Power Input
kW 0.070 / 0.073
0.105 / 0.119
1.365 / 1.418
1.54
/
1.61
Full Load Conditions Running Amps.
A
0.37
/
0.38
0.48
/
0.50
8.05
/
7.82
8.9
/
8.7
Power Input
kW 0.070 / 0.073
0.105 / 0.119
1.735 / 1.778
1.91
/
1.97
Rating Conditions
: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit
SAP – K161GJA
Outdoor Unit
SAP – C161GA