11
UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C
Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB
12
UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C
Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB
ECOi 3 Way Heat Recovery VRF Inverter Systems
Dimensions ECOi 2 Way and 3 Way (8-16 HP)
Industry’s smallest changeover boxes - fewer locating
problems
The SANYO solenoid valve kit is only 147mm high (without the
removable bracket) and takes its power from the indoor unit,
saving the cost of an additional supply.
• No additional power supply required
• Single mounting fix point
• 2 sizes avaliable (up to 5.6kW and 7.5 to 16kW)
ATK-RZP56BG and ATK-RZP160BG
Solenoid Valve Kit
HP (Combined systems)
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
Model
C0705DZH8
C0905DZH8
C1155DZH8
C1305DZH8
C1405DZH8 8 C0705DZH8 10 C0905DZH8 10 C0905DZH8
10 C0905DZH8 10 C0905DZH8 12 C1155DZH8 14 C1305DZH8 16 C1405DZH8 10 C0905DZH8 10 C0905DZH8 10 C0905DZH8 10 C0905DZH8 10 C0905DZH8 12 C1155DZH8 14 C1305DZH8 16 C1405DZH8
10 C0905DZH8 10 C0905DZH8 12 C1155DZH8
14 C1305DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 10 C0905DZH8 10 C0905DZH8 12 C1155DZH8 14 C1305DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8
14 C1305DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8 16 C1405DZH8
Power supply
380/400/415V - 3phase/50Hz
Cooling capacity
kW
22.40
28.00
33.50
40.00
45.00
50.40
56.00
61.50
68.00
73.00
78.50
85.00
90.00
96.00
101.00
107.00
113.00
118.00
124.00
130.00
135.00
Heating capacity
kW
25.00
31.50
37.50
45.00
50.00
56.50
63.00
69.00
76.50
81.50
87.50
95.00
100.00
108.00
113.00
119.00
127.00
132.00
138.00
145.00
150.00
EER Cooling
kW
3.78
3.45
3.41
3.45
3.38
3.57
3.46
3.44
3.45
3.41
3.40
3.41
3.38
3.45
3.41
3.42
3.42
3.40
3.41
3.40
3.38
COP Heating
kW
4.09
3.95
3.81
3.91
3.79
4.01
3.96
3.88
3.92
3.84
3.80
3.85
3.79
3.93
3.88
3.84
3.88
3.84
3.81
3.83
3.79
Electric ratings
Cooling
Running amperes A
10.0/9.5/9.2 13.7/13.0/12.6 16.6/15.7/15.2 20.0/19.0/18.3 23.0/21.8/21.0 23.8/22.6/21.8 27.3/26.0/25.0 30.2/28.7/27.7
33.6/31.9/30.8 36.5/34.7/33.5 39.4/37.5/36.1 43.0/40.8/39.4 45.9/43.6/42.1 47.5/45.1/43.5 50.5/48.0/46.3 53.0/51.0/49.0 57.0/54.0/52.0 60.0/57.0/55.0 63.0/60.0/58.0 66.0/63.0/60.0 69.0/65.0/63.0
Power input kW
5.93
8.12
9.82
11.59
13.31
14.10
16.20
17.90
19.70
21.40
23.10
24.90
26.60
27.80
29.60
31.30
33.00
34.70
36.40
38.20
39.90
Heating
Running amperes A
10.3/9.8/9.4 13.5/12.8/12.3 16.6/15.8/15.2 19.9/18.9/18.2 22.8/21.6/20.9 23.9/22.6/21.8 26.8/25.5/24.6 30.0/28.5/27.5
33.3/31.6/30.5 36.2/34.4/33.1 39.3/37.3/36.0 42.6/40.5/39.0 45.6/43.3/41.7 46.9/44.6/43.0 49.7/47.2/45.5 53.0/50.0/48.0 56.0/54.0/52.0 59.0/56.0/54.0 63.0/59.0/57.0 65.0/62.0/60.0 68.0/65.0/63.0
Power input kW
6.11
7.97
9.84
11.51
13.19
14.10
15.90
17.80
19.50
21.20
23.30
24.70
26.40
27.50
29.10
31.00
32.70
34.40
36.20
37.90
39.60
Recommended fuse sizes (motor rated)
32
40
32x2
1x40
1x32
2x40
2x32
1x40
1x32
2x40
3x40
Dimensions
(H/W/D) mm
1,887x890x890 (+60)
1,887x1,880x890 (+60)
1,887x1,880x890 (+60)
1887x2870x890 (+60)
Net weight
kg
290
340
580
630
680
920
970
1020
Airflow
m
3
/min
150
160
180
200
220
150+160
160+160
160+180
160+200
160+220
180+220
200+220
220+220
160+160+200 160+160+220 160+180+220 160+200+220 160+220+220 180+220+220 200+220+220 220+220+220
Piping connection
Gas
Inches (mm)
3/4 (19.05)
7/8 (22.22)
1 1/8 (28.58)
1 3/8 (34.92)
1 5/8 (41.27)
Discharge
5/8 (15.88)
3/4 (19.05)
7/8 (22.22)
1 1/8 (28.58)
1 3/8 (34.92)
Liquid
3/8 (9.52)
1/2 (12.7)
5/8 (15.88)
3/4 (19.05)
Balance
3/8 (9.52)
Operating sound normal mode
dB(A)
54.5
55.0
56.0
60.0
61.0
57.8
58.0
58.5
57.8
60.1
60.4
61.0
61.5
60.8
61.3
61.5
62.0
62.4
62.6
63.0
63.3
Operating sound quiet mode
51.5
52.0
53.0
57.0
58.0
54.8
55.0
55.5
54.8
57.1
57.4
58.0
58.5
57.8
58.3
58.5
59.0
59.4
59.6
60.0
60.3
Ambient temperature
operating range
Cooling
-10°C DB +43°C DB
Heating
-20°C DB +15°C DB
Maximum number of indoor units
13
16
19
23
26
29
33
36
40
* Condenser actual pipe connections may vary from above pipe connections shown, please refer to technical manuals for full details.
* Please refer to tube sizing charts for pipe selections and pipe length parameters.