background image

3

UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C  Heating Indoor 20˚C Outdoor 0˚C

Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB  Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB

4

UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C  Heating Indoor 20˚C Outdoor 0˚C

Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB  Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB

New PAC2 System Design Software

Designing  a  system  for  VRF  (ECOi  and  GHP)  and  PACi 

Commercial Split Systems has never been easier

SANYO  has  identified  the  importance  of  ever-increasing 
demands for fast and accurate responses to customer requests 
in our industry. More and more emphasis is being placed upon 
energy-efficiency  in  our  marketplace.  The  ability  to  calculate 
cooling/heating loads and produce information of actual design 
conditions  is  a  major  advantage  to  any  architect,  consultant, 
contractor or end user.

SANYO  understands  the  ever-changing  and  demanding 
industry  we  are  in  and  we  are  pleased  to  announce  the 
launch of the next generation of our system design software 
program. The new advanced PAC2 system design software has 
been customised to make any selection and design process as 
quick and easy as possible. The software features a version of 
AC Calc Lite. This allows small building loadings to be accurately 
calculated and directly imported into the PAC2 software.

The  design  package  utilises  system  wizards  and  import  tools 
to enable both simple and complex systems to be created. In 
addition, the system will allow outdoor and indoor units to be 
dragged  and  dropped  on  an  interactive  desktop.  This  allows 
users to create everything from realistic floor plans with detailed 
piping  and  wiring  schematics  to  send  out  with  quotations, 
through to installation guidance drawings. 

The new PAC2 system software can be used for all SANYO ECOi, GHP and PACi systems.

The new PAC2 system software can be used for all SANYO 

ECOi, GHP and PACi systems.
Features include:

• AC Calc Lite (included in the package)

 

• Easy to use system wizards

 

• Auto piping and wiring features

 

• Converted duties for conditions and pipework

 

• Auto CAD (DXF) export 

 

• Detailed wiring and pipework diagram

SANYO-Installation cost saving design

Solenoid Valve Box

Industry’s Smallest – 147mm High

• Brazed connections

• Requires only 1 Fixing for mounting

• No transmission wiring at SVK

• No mains power wiring at SVK

• Comes inclusive with lead connection to indoor unit

Saves the cost of local isolators and additional electrical 

wiring

SANYO-Intelligent on site learning

Compressor Road Map Control

• Measures the average saturated suction temperature from the 

fan coil units

• Measures the suction pressure and temperature entering the 

outdoor unit

• Calculates the best combination of compressors to run

• Targets inverter compressor at 30 – 80% (most efficient)

 Reduces the running cost of the system

SANYO-Comfort control
Air Discharge Temperature Control

• Available on U indoor ducted units

•  Discharge  air  at  below  10°C  is  uncomfortable  and  can  cause 

draughts due to cold air dumping

• Air off temperature can be controlled between 7

0

C - 22

0

C

Guaranteed user comfort

Refrigerant Volume “self check” procedure

ECOi 2 & 3WAY systems have an inbuilt self judgement mode to 
indicate the present system refrigerant volume.

From the outdoor unit you can start the self judgement mode, 
after completion (approx 30mins) the LED display’s the results.

It ensures unit efficiency, avoids refrigerant wastage and 

assists with F-Gas complince.

Unique SANYO benefits

No Control

SANYO Solution

LED 1

LED 2

Judgment mode

Blinking

Blinking

Normal

ON

ON

Insufficient gas

Blinking

OFF

Overcharge

OFF

Blinking

Judgment not possible

Blinking alternately

Summary of Contents for ECOi C0705DXHN8

Page 1: ...ly general particulars and shall not form any part of the contract For full installation details please contact your SANYO distributor Rating Conditions The cooling and heating capacities are based on the following conditions Cooling Indoor temperature 27 C DB 19 C WB Outdoor temperature 35 C DB 24 C WB Heating Indoor temperature 20 C DB Outdoor Temperature 7 C DB 6 C WB Printed using paper produc...

Page 2: ... maintenance calls and unit down time Lower running and life cycle costs SANYO ECOi VRF systems are amongst the most efficient VRF systems on the market offering COPs in excess of 4 0 at full load conditions The system is also designed to make sure that we reduce the running cost of each system by using our unique road map control routine to ensure that the most efficient combination of compressor...

Page 3: ...d out with quotations through to installation guidance drawings The new PAC2 system software can be used for all SANYO ECOi GHP and PACi systems The new PAC2 system software can be used for all SANYO ECOi GHP and PACi systems Features include AC Calc Lite included in the package Easy to use system wizards Auto piping and wiring features Converted duties for conditions and pipework Auto CAD DXF exp...

Page 4: ...s designed for creating a comfortable environment when either heating or cooling is required Heat pump systems offer heating or cooling Single footprint size for all unit capacities DC inverter technology combined with R410A for excellent efficiency System configuration from 8HP to 48HP Diversity ratio 50 130 Industry low outdoor unit sound levels from 54 5dB A Quiet mode offers a further 3dB A re...

Page 5: ...HN8 10 C0905DXHN8 10 C0905DXHN8 10 C0905DXHN8 10 C0905DXHN8 12 C1155DXHN8 14 C1305DXHN8 16 C1405DXHN8 Power supply 380 400 415V 3 phase 50 60Hz Cooling capacity kW 22 40 28 00 33 50 40 00 45 00 50 40 56 00 61 50 68 00 73 00 78 50 85 00 90 00 96 00 101 00 107 00 113 00 118 00 124 00 130 00 135 00 Heating capacity kW 25 00 31 50 37 50 45 00 50 00 56 50 63 00 69 00 76 50 81 50 87 50 95 00 100 00 108 ...

Page 6: ...mperature setting for heating operation has also been extended from 16 C to 30 C 8HP 48HP Cooling 10 C DB 43 C DB Heating 20 C WB 15 C WB Higher COPs lower running costs HP 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 EER Cooling 3 78 3 45 3 41 3 45 3 38 3 57 3 46 3 44 3 45 3 41 3 4 3 41 3 38 3 45 3 41 3 42 3 42 3 4 3 41 3 40 3 38 COP Heating 4 09 3 95 3 81 3 91 3 79 4 01 3 96 3 8...

Page 7: ... 85 3 79 3 93 3 88 3 84 3 88 3 84 3 81 3 83 3 79 Electric ratings Cooling Running amperes A 10 0 9 5 9 2 13 7 13 0 12 6 16 6 15 7 15 2 20 0 19 0 18 3 23 0 21 8 21 0 23 8 22 6 21 8 27 3 26 0 25 0 30 2 28 7 27 7 33 6 31 9 30 8 36 5 34 7 33 5 39 4 37 5 36 1 43 0 40 8 39 4 45 9 43 6 42 1 47 5 45 1 43 5 50 5 48 0 46 3 53 0 51 0 49 0 57 0 54 0 52 0 60 0 57 0 55 0 63 0 60 0 58 0 66 0 63 0 60 0 69 0 65 0 ...

Page 8: ...75XH SPW UR74GXH56B SPW U095XH SPW UR94GXH56B SPW U125XH SPW UR124GXH56B SPW U165XH SPW UR164GXH56B SPW U185XH SPW UR184GXH56B SPW U255XH SPW UR254GXH56B SPW U365XH SPW UR364GXH56B SPW U485XH SPW UR484GXH56B SPW U605XH SPW UR604GXH56B DR Type Concealed Duct SPW DR254GXH56B SPW DR364GX H56B SPW DR484GX H56B SPW DR764GXH56B SPW DR964GXH56B K Type Wall Mounted Unit SPW K075XH SPW K095XH SPW K125XH KR...

Page 9: ...trol for setting Centralised control systems Operation with various function from central station Only ON OFF operation from central station Simplified charge ratio for each tenant Touch screen panel Personal computer field supply External appearance Type model name System controller SHA KC64AGB ON OFF controller SHA KC16KAGB Intelligent controller SHA KT256EG Communication adaptor SHA KA128AGB Nu...

Page 10: ...a subject to change without notice Fresh air Exhaust air Return air Supply air Humidification optional DX coil Heat exchanger Installation example Timer remote controller RCS TM80BG Simplified remote controller RCS KR1EG Wireless remote controller Controller Options RCS BH80BG WL Rating Conditions Cooling Indoor 27 C DB 19 C WB Outdoor 35 C DB 24 C WB Heating Indoor 20 C DB Outdoor 7 C DB 6 C WB C...