37
8-4. Fan Speed Control
During Cooling Operation Automatic fan speed
T
S
+ 4
°
F (2
°
C)
3 minutes
OFF
T
S
+ 2
°
F (1
°
C)
Set Value (T
S
)
H
M
L
ON
OFF
Fan Speed
Compressor
3 minutes
ON
T
R
:
Room temp.
T
S
– 2
°
F (1
°
C)
Ts
T
S
+ 2
°
F (1
°
C)
30 seconds
30 seconds
H
M
LL
Compressor ON
Compressor OFF
Fan Speed
T
R
:
Room temp.
*
For 3 minutes after power ON, the compressor does not turn on.
*
For 30 seconds after the compressor is turned OFF, the previous fan speed is maintained.
During Heating Operation Automatic fan speed