11. PROCESSES AND FUNCTIONS
Fig. 8
(1)
Room Temperature Control
The Unit adjusts room temperature by turning the outdoor unit’s compressor ON and OFF.
This process is controlled by the thermostat located in the remote control unit.
The figures on this and the next pages show how each part of the system performs when the
room temperature changes and the thermostat activates the compressor to start (thermo ON)
or stop (thermo OFF). Fig. 8 shows about the cooling cycle.
Chart Summary and Explanations
❑
Once the compressor starts, it keeps running for 5 minutes.
❑
Once the compressor stops, it will not start running again for 3 minutes.
❑
If you change the operation mode during the cooling cycle, the control circuit stops the
compressor for 3 minutes.
❑
For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off,
the compressor is not controlled by the room sensor.
❑
Thermo ON: When room temperature rises 1
°
F above the set temperature T˚, (T ˚+1
°
F):
Compressor
➞
ON
❑
Thermo OFF: When the room temperature is equal to or below the set temperature T˚:
Compressor
➞
OFF
THERMO ON
ROOM TEMPERATURE
THERMO ON
S. T.+ 1
°
F
SET TEMP. T
°
F
(S.T.)
COMPRESSOR
OFF
OFF
WITHIN 3 MINUTE
MORE THAN
5 MINUTES
ON
ON
ON
1028_X_S
OFF
OFF
INDOOR FAN
OUTDOOR FAN
SET SPEED (MANUAL)
THERMO OFF
3 MINUTES
THERMO OFF
MORE THAN 3 MINUTES
ON
ON
ON