4
4
- 6
2. Detailed Settings Function
W-2WAY ECO-i SYSTEM
Remote Controller Functions
Item code
Item
Setting data
No.
Description
(1B)
Forced thermostat ON time
0000
5 minutes
0001
4 minutes
Cooling discharge
temperature shift
–010
–20°F
–009
–18°F
–008
–16°F
0010
20°F
Heating discharge
temperature shift
–010
–20°F
–009
–18°F
–008
–16°F
0010
20°F
Temperature shift for
cooling/heating change in
auto heat/cool mode
0001
±2°F
0002
±4°F
0003
±6°F
0007
±14°F
(Upper limit)
Change to remote
control temperature
setting range
Cooling
0018
64°F (Lower limit at shipment)
0019
66°F
(Lower limit)
0029
84°F
0030
86°F (Upper limit at shipment)
(Upper limit)
Heating
0016
60°F (Lower limit at shipment)
0017
62°F
(Lower limit)
0029
84°F
0030
86°F (Upper limit at shipment)
(Upper limit)
Dr
ying
0018
64°F (Lower limit at shipment)
0019
66°F
(Lower limit)
0029
84°F
0030
86°F (Upper limit at shipment)
(Upper limit)
A
uto heat/cool
0017
62°F (Lower limit at shipment)
0018
64°F
(Lower limit)
0026
78°F
0027
80°F (Upper limit at shipment)
Humidifier operation
0000
Normal
0001
Ignore heat exchanger temperature conditions.
Filter (CN70) input
switching
0000
Filter input (differential pressure switch input)
0001
Alarm input (for trouble input about air cleaner or similar device)
0002
Humidifier input (Operates linked with drain pump when humidifier is
ON.)
Indoor unit electronic
control valve
0000
Present (Setting at shipment)
0002
None
T10 terminal switching
0000
Normal (Used as optional relay PCB or JEMA standard HA terminal.)
0001
Used for OFF reminder
0002
Fire prevention input