COILCLEAN IL INSTALLATION MANUAL

Version 08/2017

QUESTIONS ON INSTALLATION?

CALL SANUVOX AT 1-888-726-8869

J

I

K

L

A. High-intensity UVC germicidal lamp

B. Anodized aluminum parabolic reflector

C. Clamp assembly

D. 3/4" support rod

E. Mounting flange (2)

F. Gaynor lamp plug

G. UV lamp boot

H. Teflon wire set (20 feet)

I. Ballast box

Also includes:

J. Coupler

K. Cotton gloves & hardware

L. UV caution decal

A

B

C

D

E

F

G

H

SAFETY CONSIDERATIONS

SELECTING THE APPROPRIATE LOCATION

Installation and servicing of air-conditioning 

equipment can be hazardous due to system 

pressure and electrical components. Only 

trained and qualified service personnel 

should install, repair, or service air-

conditioning equipment.

Untrained personnel can perform basic 

maintenance functions such as changing 

lamps. All other operations should be 

performed by trained service personnel. 

When working on air-conditioning equipment, 

observe precautions in the literature, tags 

and labels attached to the unit or accessory, 

and other safety precautions that may apply. 

Follow all safety codes. Wear safety glasses 

and work gloves.

Refer to your customized Sanuvox sizing & placement proposal as to where 

the CoilClean ILs are to be installed. 

IL's can be installed on the upstream or downstream side of the coil. If you do not 

have  the

 

Sanuvox  sizing  &  placement  proposal,  call  1-888-726-8869  where 

Sanuvox will provide one at no-charge.

Before installing or performing maintenance or 

service on the unit, turn off unit and disconnect from 

power source. Electrical shock can cause injury or 

death. There may be more than one disconnect 

switch.

__________________________

__________________________

__________________________

__________________________

Never expose eyes or skin to ultraviolet light from any 

source. The unit MUST be DISCONNECTED from 

power source before performing maintenance or 

service. Personal injury may result.

Do not touch lamp glass without gloves. Reduced 

performance of lamp may result. Clean lamp after 

handling.

The UV lamp contains a small quantity of mercury. 

If a lamp breaks, clean and dispose of with care.

Use only specified replacement lamps with your unit. 

Use of an incorrect lamp can result in damage to the 

unit and/or lamp.

WARNING

IMPORTANT NOTICE

The  whole  assembly  must  be  field-installed  inside  the  air  handling  unit,  either 

horizontally to the side panels, or on the coil frame, using field-mounted brackets or 

vertically, to floor and ceiling of AHU. Make sure that the site can be supplied with the 

necessary power requirements. Power consumption is 1.0 amp for 40'' lamps, 1.25 

amps for 50” lamps and 1.5 amps for 60” lamps. Ensure that there is adequate 

clearance for service. If a humidifier is present, the ideal location for the germicidal 

coil cleaner is in the air stream before the humidifier. If space does not permit, the 

germicidal  coil  cleaner  may  be  installed  after  the  humidifier.  The  operating 

temperature range is 50 to 115 F. Operating outside of this range will result in 

decreased performance.

NOTE: The CoilClean IL is NOT waterproof. If installed outdoors, CoilClean IL 

fixture  and  ballast  boxes  must  be  installed  in  a  watertight  and  ventilated 

enclosure.

MAINTENANCE

CERTIFICATIONS

UNDERSTANDING BALLAST LED DISPLAY & DRY CONTACTS

UV SYSTEM ‘ON’ : The system is functioning normally
UV LAMP TO BE REPLACED : Notifies the user that the lamp

has reached the end of its serviceable life (24 months of real-

time operation) and must be replaced
UV LAMP FAILURE :

powered ON with no UV lamp installed

Flashes if lamp has failed or the unit is 

NO POWER (LED OFF) : There is no power being delivered to the 

system or defective power supply

The CoilClean IL  incorporates unique features into the ballast control box. These include LED status 

display as well two pairs of dry contacts designed to communicate with building automation systems.

LED status display

The  ballast box may have one or two ballasts incorporated into the box depending on how many units 

were ordered. If only one ballast is incorporated into the ballast box, you will notice only one wire set 

incorporated into the box and a black button covering where a second LED would be. If  the ballast 

box incorporates two ballasts there will be two LEDs that corresponding to each UV lamp. 

A reset button is located under the LED (when cover is removed) allowing the user to “Reset” the timer 

back to zero. To be performed after UV lamp replacement.

Dry contacts for building automation integration

Each  CoilClean IL system includes a pair of dry contacts (NO & NC). Dry contacts make it possible for 

the CoilClean ILs to be easily tied to a building automation system.

 Maximum voltage to be provided to 

common is 30VDC.

(Green)
(Yellow)

(Red)

(LED OFF)

Reset

LED

NO: normally open

NC: normally closed

               

CoilClean IL replacement UV lamps

LMPHGS120: T6 High-Intensity Germicidal (UVC) 12” Straight UV Lamp for IL12

 

LMPHGS180: T6 High-Intensity Germicidal (UVC) 18” Straight UV Lamp for IL18

 

LMPHGS240: T6 High-Intensity Germicidal (UVC) 24” Straight UV Lamp for IL24

 

LMPHGS300: T6 High-Intensity Germicidal (UVC) 30” Straight UV Lamp for IL30

 

LMPHGS400: T6 High-Intensity Germicidal (UVC) 40” Straight UV Lamp for IL40

 

LMPHGS500: T6 High-Intensity Germicidal (UVC) 50” Straight UV Lamp for IL50

 

LMPHGS600: T6 High-Intensity Germicidal (UVC) 60” Straight UV Lamp for IL60

CoilClean IL replacement ballast

Multi voltage BST120/277SHS for IL12, IL18, IL24 IL30, IL40, IL50, IL60

Others

FLANGE part# MSC9

FLANGE ADAPTOR

 part# MSCCON19

LIMIT SWITCH part# MSCSWC14

PART NUMBERS

Lamp Change-Out: 17,000 hours (2 years) 

Disconnect all power before performing any 

maintenance or service. UV lamps need periodic 

replacement to maintain design specifications. Replace 

UV lamps after 17,000 hours of operation. Use caution 

when removing and inserting UV lamps from the metal 

spring clamps. Then press on the reset button for 

resetting timer to zero.  

Use only specified Sanuvox UV lamps with this UV 

system. Other UV lamps may plug into the connector, 

but they should not be used. The use of an incorrect 

lamp can result in damage to the system or UV lamp 

and void the warranty.

NO: normally open

NC: normally closed

Common

DRY CONTACTS

UV lamp can be disposed/recycle after use as for any 

other fluorescent bulb. 

CoilClean ILs are designed for continous operation. 

Do not cycle the system through a relay connected to 

the fan blower.

__________________________

CSAC22.2 113#Issue: 2015/05/01 Fans and ventilation

UL 507  Issued: 1999/12/13 Ed: 9 Rev. 2012/06/18 Electric Fans

 

Marking : cETLus

WARRANTY

Lamp Warranty: 2 years

Electronics: 1 year

Ballast Warranty: 15 years

SIGNAL READING

NO

NC

Same as 

common

1

0V

2

0V

2

Same as 

common

1

1 or 2 lamps 

are OFF

Lamps are

ON

1

circuit is opened 

 2

circuit is closed

Reviews: