Santon AH10/2.2 Installation And User Instructions Manual Download Page 7

  7

4.0 INSTALLATION - DISCHARGE PIPE REQUIREMENTS

4.1

  The discharge outlet from the Pressure (Expansion) Relief Valve and the             

Temperature/Pressure Relief Valve (if fitted) must be connected to a discharge 

pipe. It is recommended that a tundish (not supplied) be installed in the discharge 

pipe to give a visible indication that the valves are operating.

4.2

  The discharge pipe must fall continuously from the valve outlets and be               

unobstructed.

4.3

  The pipe from the valves to the tundish should be 15mm o/dia minimum. From 

the tundish to the point of discharge the pipe should be 22mm o/dia minimum and 

have a resistance to flow equivalent to 9 metres of straight pipe. Long discharge 

pipe runs should have an increased internal diameter.

4.4

  The pipe material should be capable of conveying water/steam at 100

o

C.

4.5

  The final discharge point should be in a safe, visible position.

7

5.0 COMMISSIONING

5.1

  Do not switch on the electrical supply until the unit has been filled with water and 

checked for leaks.

5.2

  Check that all installation, electrical and discharge pipe requirements have been 

met.

5.3

  Check that all water and electrical connections are tight.

5.4

  Open a hot water tap, turn on mains water supply to the heater.

5.5

  Allow unit to fill and leave hot tap running for a short while to purge any air and 

flush out the pipework. Close the hot tap and check the system for leaks.

5.6

  Manually test the operation of the Pressure (Expansion) Relief Valve and, if 

fitted, the Temperature/Pressure Relief Valve. Ensure water flows freely from the 

valve(s) and through the discharge pipes.

5.7

  Switch on the electrical supply. The indicator light will illuminate during heating. 

When the set temperature is reached the indicator light will go out.

5.8

 The set temperature can be adjusted by rotating the shaft located on the Combined 

Thermostat and Thermal Cut-out, clockwise increases the temperature. Access to 

adjust the temperature is gained by removing the terminal cover 

.

6.0 REMOVAL AND FITTING OF TERMINAL COVER

6.1 

To remove the terminal cover  use a large flat bladed screwdriver to relieve the   

      snaps located towards the front at either side of the cover. Gripping the cover at   

      the front, pull  upwards.

6.2 

To fit the cover, locate the hinge at the back. Slide the snaps into place. Apply 

      pressure to the front of the cover pushing back and down until it snaps securely 

      in place.

Summary of Contents for AH10/2.2

Page 1: ...read and understand these instructions before starting work Please leave this leaflet with the user following installation PACK CONTENTS Heater Pressure relief valve Fixing screws and plugs Installation and User Instructions WARNING This water heater must only be installed by qualified persons 36005791 Issue 3 ...

Page 2: ...W 15l 2 2kW Storage volume V litres 7 0 10 0 15 0 Mixed water 40 C V40 l 13 17 25 Load Profile XXS XXS XXS Energy Efficiency Class C C C Energy Efficiency 31 3 30 6 30 8 Annual electricity consumption kWh 589 603 599 Daily fuel consumption kWh 2 860 2 940 2 920 Thermostat setting 60 C Specific precautions that shall be taken when the water heater is assembled installed or maintained and disposed o...

Page 3: ...ditions in 1 2 above cannot be met expansion must be accomodat ed using an Expansion Vessel To ensure all expansion takes place in the vessel a Non Rerturn Valve must also be fitted together with a Pressure Expansion Relief Valve see Figure 2 Use Accessory Pack ALK05 94970012 1 4 If the static supply pressure exceeds 4 1 bar 60p s i a Pressure Reducing Valve must be fitted to the cold main supply ...

Page 4: ...T COLD DRAW OFF SERVICE VALVE COLD WATER MAINS 2 0 7L 2 8 10L OR 4 2 15L METRES IS REQUIRED FOR EXPANSION IN PIPEWORK FIGURE 1 FOR INLET WATER PRESSURES UP TO 4 1 BAR 60 P S I NO ADDITIONAL KITS USED COLD EXPANSION VESSEL NON RETURN VALVE NEAREST COLD DRAW OFF SERVICE VALVE COLD WATER MAINS FIGURE 2 FOR INLET WATER PRESSURES UP TO 4 1 BAR 60 P S I WHERE EXPANSION IN MAIN SUPPLY IS NOT POSSIBLE USI...

Page 5: ...ricity gas or water below the surface of the wall 2 5 DO NOT install where the unit may freeze 2 6 Refer to the section IMPORTANT INSTALLATION POINTS to determine which valves and accessories are required Plumb in the valves in the sequence shown in the relevant Diagrams Figures 1 2 and 3 2 7 Both inlet and outlet pipes are clearly labeled The pipes are 15mm copper tube and are suitable for compre...

Page 6: ...CT 3 0 INSTALLATION ELECTRICAL REQUIREMENTS WARNING This appliance must be earthed It is suitable for a c supply only Disconnect the electrical supply before removing the terminal cover Installation must be in accordance with the current I E E Wiring Regulations 3 1 The unit is supplied fitted with a 0 75m 3 core 1 5mm2 flexible cable The electic ity supply should be fused 13 Amp and be via a doub...

Page 7: ...n met 5 3 Check that all water and electrical connections are tight 5 4 Open a hot water tap turn on mains water supply to the heater 5 5 Allow unit to fill and leave hot tap running for a short while to purge any air and flush out the pipework Close the hot tap and check the system for leaks 5 6 Manually test the operation of the Pressure Expansion Relief Valve and if fitted the Temperature Press...

Page 8: ... unit through the outlet connection 7 3 Remove the terminal cover as described in Section Six 7 4 Disconnect the electrical terminations to the thermostat Disconnect earth links to the earthing stud 7 5 Remove the element plate assembly by unscrewing the five securing screws tapped jacking points are provided Remove any loose scale from the container Carefully clean off any scale from the element ...

Page 9: ...re 95 614 274 Terminal cover 15 litre 95 614 275 8 0 MAINTENANCE SAFETY VALVES The Pressure Expansion Relief Valve and if fitted the Temperature Pressure Relief Valve should be regularly checked Manually operate the valves by either twisting the cap or lifting the lever Ensure water flows freely from the valve s and through the discharge pipes Ensure the valve s reseat correctly when released 9 0 ...

Page 10: ... intermittently Presure Relief Valve Discharge of water from 1 Fit pack ALK05 94970012 see IMPORTANT INSTALLATION POINTS 2 Fit pack ALK04 94970011 see IMPORTANT INSTALLATION POINTS 3 Replace Pressure Relief Valve 4 Check and if necessary re charge Expansion Vessel pre charge pressure see Section 9 0 1 Expansion in mains not possible 2 Mains pressure exceeds 4 1 bar 60 p s i 3 Pressure Relief Valve...

Page 11: ... of freezing when the heater is not in use for long periods during the winter months do not switch off the electrical supply and set the thermostat to its minimum position N B This will not protect other system pipework 13 2 The indicator light will be illuminated when the unit is heating 13 3 To ensure the heater continues to operate at its optimum performance it should be periodically maintained...

Page 12: ...e unit has been used only for heating potable water The unit is not guaranteed against damage by frost and the inner container with integral immersion heater is not guaranteed against excessive scale build up This Guarantee in no way affects the statutory rights of the consumer The policy of Santon is one of continuous product development and as such we reserve the right to change specifications w...

Reviews: