![Santerno SUNWAY TG1200 1000V TE OD Installation Manual Download Page 131](http://html1.mh-extra.com/html/santerno/sunway-tg1200-1000v-te-od/sunway-tg1200-1000v-te-od_installation-manual_810313131.webp)
INSTALLATION GUIDE
MODULAR SUNWAY TG
TE OD
Rev. 03
– 01/06/2018
131/
139
No.
Name
Description
I/O Features
DIP-switch
13
CMA
0V for analogue outputs (connected to
control 0V).
Table 54: Terminals 1 - 13 available on the control board
No.
Name
Description
I/O Features
DIP-switch
14
MDI1
Digital input
Please refer to the Electrical and
Mechanical diagram
Optoisolated digital
inputs 24 Vdc: positive
logic (PNP type) active
with high signal in
relation to CMD (terminal
22).
15
MDI2
(ENABLE)
Input active: inverter enabled to run
Input not active: inverter disabled
16
MDI3
Digital input
Please refer to the Electrical and
Mechanical diagram
17
MDI4
Digital input
Please refer to the Electrical and
Mechanical diagram
18
MDI5
Digital input
Please refer to the Electrical and
Mechanical diagram
19
MDI6
Digital input
Please refer to the Electrical and
Mechanical diagram
20
MDI7
Digital input
Please refer to the Electrical and
Mechanical diagram
21
MDI8
Digital input
Used for carrier phase synchronization
22
CMD
0V digital input isolated in relation to
control 0V
Used for carrier phase synchronization
Optoisolated 0V digital
inputs
23
+24V
Auxiliary power supply output for digital
inputs.
Used for carrier phase synchronization
+24 V±15%
max: 100 mA
Protected by self-
resetting fuse
24
+VMDO1
Power supply input for MDO1 output
Used for carrier phase synchronization
20 ÷ 48 Vdc
Isc = 10 mA + output
current (max 60 mA)
25
MDO1
/FOUT
Multifunction digital output 1: frequency
output
Used for carrier phase synchronization
Push-pull optoisolated
digital output
Iout = 50 mA max
fout max 100 kHz.
26
CMDO1
0V multifunction digital output 1
Used for carrier phase synchronization
MDO1 common power
supply and output