ASSEMBLY
INSTRUCTIONS
PARALLEL-CONNECTED
SINUS PENTA MODELS
6/
24
Drive size
Drive
model
N. of
drives to
be parallel
connected
Final
size
Final
model
Applicable motor power with overload up to 120%
Inom Imax
525-575Vac
660-690Vac
kW
HP
A
kW
HP
A
A
A
S42
0259
2
S44 0459
630
860
720
710
970
696
720 880
S52
0290
2
S54
0526
710
970
800
800
1090
773
800 960
0314
0600
800
1090
900
900
1230
858
900 1100
0368
0750
900
1230
1000
1000
1360
954
1000 1300
0401
0828 1000 1360
1145
1240
1690
1200
1200 1440
S52
0368
3
S56
0960 1270 1730
1480
1530
2090
1480
1480 1780
0401
1128 1460 1990
1700
1750
2380
1700
1700 2040
Drive supply voltage
525-575Vac
525-575Vac
Table 2: Drive sizes that can be obtained when applying 500V to 690V supply voltage
Key:
Inom
= continuous rated current of the drive
Imax
= maximum current that can be delivered by the drive for 60s every 10 min.
CAUTION
The drive size to be obtained involves configuring the drive electronic boards
accordingly. Specify the drive configuration to be otabined at the same time as
ordering the equipment.
CAUTION
Do not change the layout and wiring covered in this manual when parallel
connecting the SINUS PENTA drives. Any configuration other than that covered
in this manual is not allowed and may damage the equipment or lead to
equipment malfunction.