background image

 15P0102B200 

 

SINUS  PENTA 

 
 

ASSEMBLY INSTRUCTIONS 

FOR SINUS PENTA 

S41 S42 S51 S52  

PARALLEL-CONNECTED 

MODELS 

 

Issued on 09/05/2018 
R.01 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

 

 

 

Elettronica Santerno S.p.A. 

Via della Concia, 7 - 40023 Castel Guelfo (BO) Italia 

Tel. +39 0542 489711 -  Fax +39 0542 489722 

santerno.com

     

[email protected]

 

  This manual  is  integrant and  essential  to the  product.  Carefully  read  the  instructions  contained  herein  as 

they provide important hints for use and maintenance safety. 

 This device is to be used only for the purposes it has been designed to. Other uses should be considered 

improper  and  dangerous.  The  manufacturer  is  not  responsible  for  possible  damages  caused  by  improper, 
erroneous and irrational uses. 

 Elettronica Santerno is responsible for the product in its original setting. 

  Any  changes  to  the  structure  or  operating  cycle  of  the  product  must  be  performed  or  authorized  by 

Elettronica Santerno. 

 Elettronica  Santerno assumes no responsibility for the consequences resulting  by  the  use  of non-original 

spare-parts. 

  Elettronica  Santerno  reserves  the  right  to make  any  technical  changes  to this  manual  and  to the  product 

without  prior  notice.  If  printing  errors  or  similar  are  detected,  the  corrections  will  be  included  in  the  new 
releases of the manual. 

  The  information  contained  herein  is  the  property  of  Elettronica  Santerno  and  cannot  be  reproduced. 

Elettronica Santerno enforces its rights on the drawings and catalogues according to the law. 

E n g l i s h  

Summary of Contents for SINUS PENTA S41

Page 1: ...ible damages caused by improper erroneous and irrational uses Elettronica Santerno is responsible for the product in its original setting Any changes to the structure or operating cycle of the product...

Page 2: ...ions Guide revision R 01 have been changed in respect to the previous Assembly Instructions Guide revision R 00 Logo with ENERTRONICA GROUP Nameplates of the drive OTHER USER MANUAL MENTIONED IN THIS...

Page 3: ...S 12 4 1 1 POWER COMPONENTS PARALLEL CONNECTED DRIVE SUPPLY MAINS 13 4 1 1 1 4T Class 13 4 1 1 2 5T 6T Class 13 4 1 2 POWER COMPONENTS DRIVE SUPPLY LINES 14 4 1 2 1 4T Class 14 4 1 2 2 5T 6T Class 14...

Page 4: ...ematic for N 3 parallel connected drives 11 Figure 5 Mechanical features of a 3 phase input inductor 23 Figure 6 Mechanical features of a 3 phase output inductor 24 0 3 Tables Table 1 Drive sizes that...

Page 5: ...NTA Installation Guide The sizes that can be obtained by parallel connecting Sinus Penta drives S41 S51 S42 S52 are given in Table 1 and Table 2 Drive size Drive model N of drives to be parallel conne...

Page 6: ...480 1780 0401 1128 1460 1990 1700 1750 2380 1700 1700 2040 Drive supply voltage 525 575Vac 525 575Vac Table 2 Drive sizes that can be obtained when applying 500V to 690V supply voltage Key Inom contin...

Page 7: ...lave 0401 Last Slave 2 Table 3 Components of the kit to assemble a drive composed of parallel connected elements NOTE Flat cables are inside the slave drives see section 4 1 4 Make sure that the equip...

Page 8: ...master and slave s is described and identified by a nameplate located on the master drive side A nameplate example is given in Figure 1 Data related to parallel connected drives are given on nameplate...

Page 9: ...the control board and it is always installed on the left hand side of the slave drives First Slave drive this is the slave installed in the middle position when there are N 3 parallel connected drive...

Page 10: ...lled inside a cabinet Do the following 1 Do not exceed maximum clearance between the drives 2 Make sure that the path of the flat cable for the control signals is clear in particular the flat cable mu...

Page 11: ...S T U V W GROUND AC LINE REACTOR INPUT FUSES CIRCUIT BREAKER AC POWER SUPPLY S000720 Figure 4 Electrical schematic for N 3 parallel connected drives CAUTION Always install the fuse failure detection...

Page 12: ...ightening torque for the terminals to the bar connections For connections to bars the tightening torque relates to the bolt tightening the cable lug to the copper bar The cross section values given in...

Page 13: ...1000 0749 1000 10 40 1250 1250 1000 0832 1200 10 50 1400 1400 1250 S55 0850 1340 10 63 1500 1500 1400 0965 1480 10 80 1800 1800 1600 1129 1700 10 100 2000 2000 1800 4 1 1 2 5T 6T Class Size SINUS PENT...

Page 14: ...rms 630 S51 0313 480 4 40 2x150 2x300kcmils 0 031mH 720Arms 700 0367 550 5 40 2x185 2x350kcmils 800 0402 680 6 40 2x240 2x500kcmils 1000 4 1 2 2 5T 6T Class Size SINUS PENTA Model Drive line current C...

Page 15: ...the Canadian Standard Size SINUS PENTA Model UL approved Fuses Manufactured by SIBA Sicherungen Bau GmbH 200 kARMS Symmetrical A I C Bussmann Div Cooper UK Ltd 100 200 kARMS Symmetrical A I C Mod N R...

Page 16: ...2x350kcmils 0402 680 2x240 2x500kcmils 4 1 3 2 6T Class Size SINUS PENTA Model Drive output current Cross section of the motor cable Output inductor A mm2 AWG kcmils mH A S42 0259 400 2x120 2x250kcmi...

Page 17: ...the control board please refer to the SINUS PENTA Installation Guide A special cable supplied with the drives to be parallel connected is required One or two cables will be supplied based on the numb...

Page 18: ...ASSEMBLY INSTRUCTIONS PARALLEL CONNECTED SINUS PENTA MODELS 18 24 Remove the terminals cover 1 Remove the main cover...

Page 19: ...e drives 3 Plug the flat cable to connector CN2 on the ES884 control board on the master drive CAUTION Remove the main cover carefully to avoid damaging the connector of the keypad cablet located on t...

Page 20: ...at cable to connector CN4 on the ES884 control board on the first slave drive if fitted otherwise go to step 5 5 Plug the second cable to connector CN2 on the ES884 control board on the first slave dr...

Page 21: ...RUCTIONS 21 24 7 Reassemble the main cover on the drives Make sure that the flat cables enter the special openings Follow the instructions given above in the reverse order 8 Reassemble the top cover t...

Page 22: ...0260 IM0126332 0 05 mH 455Arms IM0138250 0 035mH 440Arms 120 S51 0313 IM0126372 0 031mH 720Arms IM0138300 0 025mH 700Arms 120 0367 0402 5 2 Three phase Input and Output Inductors 6T Class DRIVE SIZE...

Page 23: ...050 455 C 300 317 217 100 250 128 9x24 54 410 IM0126372 Input only 0 031 720 C 360 342 268 120 325 176 9x24 84 700 5 2 1 2 5T 6T Class 3 Phase Inductors Figure 5 Mechanical features of a 3 phase inpu...

Page 24: ...NDUCTOR RATINGS DIMENSIONS HOLEWEIGHT LOSSES mH A TYPE L H P M E G mm kg W IM0138250 Output only 0 035 440 B 360 401 268 120 250 200 12x25 75 710 IM0138300 Output only 0 025 700 B 360 411 279 120 250...