-74-
Code
Function name
Data content
Minimum
unit
Factory
value
3011
PID1 calculus of polarity switching
1: command value-feedback value
2: feedback value- command value
1
1
3012
PID1 gain polarity switching
1: same gain for positive and negative deviations
2: different gain for positive and negative
deviations
1
1
3013
PID1 command value gain
0
~
50
0.01
1
3014
PID1 feedback value gain
0
~
50
0.01
1
3015
PID1 control of proportional gain
(negative: F3012=2)
0
~
100
0.01
0.1
3016
PID1 control of integration time
(negative: F3012=2)
0.01
~
100 seconds
0.01 second
0.1
3017
PID1 control of command value
0
~
6000
0.1
0
3018
PID1 control of feedback value
(communication function)
0
~
6000
0.1
0
3019
PID1 control of corresponding frequency
of maximum command value
0
~
400Hz
0.01Hz
50
3101
PID2 switch of command value input
1: frequency
2: external analog VRF voltage (0
~
5V)
3: external analog VRF voltage (0
~
10V or
potentiometer)
4: external analog V/I voltage (0
~
5V)
5: external analog V/I voltage (0
~
10V or
potentiometer)
9: external analog V/I current (4
~
20mA)
11: function code setting (F3117)
1
1
Summary of Contents for LeaderSamco NS
Page 7: ......
Page 8: ...7 1 Safety 1 1 Important notes 1 2 Instructions for use...
Page 9: ...8 1 3 Instructions for installation 1 4 Instructions for transportation and relocation...
Page 10: ...9 1 5 Instructions for wiring...
Page 11: ...10 1 6 Instructions for operation 1 7 Instructions for maintenance and examination...
Page 12: ...11 1 8 Instructions for disposal 1 9 other notes...
Page 22: ...21 4 Connection layout 4 1 Terminal power connection diagram...
Page 24: ...23 4 2 2 Main circuit terminal layout 1 NS 4A003 B NS 4A004 B NS 4A006 B NS 2A003 A NS 2A004 A...
Page 25: ...24 2 NS 4A009 B NS 4A013 B NS 4A017 B...
Page 26: ...25 3 NS 4A024 B NS 4A032 B NS 4A038 B NS 4A046 B...
Page 36: ...35 4 6 Connection to peripheric equipment 4 6 1 Peripheric equipment connection diagram...