6

Note, if the Actual Measured CFM is not enough, the installer may need to increase the duct size or add 

a booster fan if necessary. Ensure there is no blockage in the ductwork first.

 

9.    MAINTENANCE

CAUTION: BEFORE CARRYING OUT ANY MAINTENANCE OR SERVICING, ENSURE THE UNIT IS 

DISCONNECTED FROM THE MAIN ELECTRICAL SUPPLY.

S&P recommends inspection of the MD6 and ES24V at least once every twelve (12) months. To 

inspect the unit disconnect from electrical supply. Remove the MD6 motorized damper from the fresh 

air ductwork and inspect the damper blade for damage and proper function. If any debris is evident on 

the damper blade clean with a damp (not wet) cloth. DO NOT USE any detergents or abrasive materials 

for cleaning. Reinstall MD6 motorized damper to the fresh air ductwork and reseal joints. 

Airflow / Air Velocity Reference Table

Airflow 

(CFM)

Duct Size (in)

6

7

8

Air Velocity (FPM)

30

153

112

86

40

204

150

115

50

255

187

143

60

306

225

172

70

357

262

201

80

407

299

229

90

458

337

258

100

509

374

286

110

560

412

315

120

611

449

344

130

662

486

372

140

713

524

401

150

764

561

430

160

815

599

458

170

866

636

487

180

917

674

516

190

968

711

544

200

1019

748

573

Summary of Contents for MD6-ES24VK

Page 1: ...pose of this manual is to aid in the proper installation and operation of fans manufactured by S P USA These instructions are intended to supplement good general practices and are not intended to cover detailed instruction procedures because of the wide variety and types of fans manufactured by S P USA 6393 Powers Ave Jacksonville FL 32217 P 800 961 7370 F 800 961 7379 MD6 ES24VK IOM_v 1 06 2018 M...

Page 2: ......

Page 3: ...ation NFPA and the American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local code authorities 5 When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities 6 Ducted fans must always be vented to the outdoors 2 PRE INSTALLATION INSPECTION The MD6 ES24VK has been manufactured in accordance with rigorous standards of pr...

Page 4: ...ed between the fresh air wall cap roof cap soffit vent with insect screen and the HVAC unit return duct The ES24V fresh air control can be mounted On the 6 insulated ductwork between the wall cap and the MD6 motorized damper or Note the 24V power wires R C will need to be extended from the HVAC unit power supply or a separate 120V 24V transformer On the HVAC unit Note the temperature 26AWG cable a...

Page 5: ... smaller ducts than recommended Insulation around the ducts can reduce energy loss and inhibit mold growth Ductwork connections and penetrations should be sealed with duct tape duct fast clamps or caulk available through your local distributor to create an air tight path from the building exterior to the ventilated space 6 WIRING CAUTION Ensure that power is turned off and locked out before making...

Page 6: ...DAMPER CLASS II POWER SUPPLY CAN COME FROM HVAC TRANSFORMER IF ADEQUATE OR AUXILIARY TRANSFORMER IF NECESSARY SENSOR SENSOR C TS TS R G R C G G C R FIGURE 2 ES24V 20VA NOT AVAILABLE FOR DIRECT CONNECTION OF MOTORIZED DAMPER COMMON TRANSFORMER R C G G C R SENSOR G R TS TS C SENSOR Refer to the ES24V Envirosense Ventilation Control IOM on pages 8 9 for ES24V wiring connections and operation ...

Page 7: ...V to the OFF position and calculate the required continuous CFM based on the ventilation code ASHRAE 62 2 2010 Required Continuous CFM 0 01 Floor Area in ft 7 5 of bedrooms 1 Example 2 000 square foot dwelling 3 bedrooms 50 CFM continuous ASHRAE 62 2 2013 2016 Required Continuous CFM 0 03 Floor Area in ft 7 5 of bedrooms 1 Example 2 000 square foot dwelling 3 bedrooms 90 CFM continuous Now that th...

Page 8: ...zed damper from the fresh air ductwork and inspect the damper blade for damage and proper function If any debris is evident on the damper blade clean with a damp not wet cloth DO NOT USE any detergents or abrasive materials for cleaning Reinstall MD6 motorized damper to the fresh air ductwork and reseal joints Airflow Air Velocity Reference Table Airflow CFM Duct Size in 6 7 8 Air Velocity FPM 30 ...

Page 9: ...f the fault THE FOLLOWING WARRANTIES DO NO APPLY Damages from shipping either concealed or visible Claim must be filed with the carrier Damages resulting from improper wiring or installation Damages caused by acts of nature or resulting from improper consumer procedures such as Improper Maintenance Misuse Negligence Alteration Abuse Abnormal Use or Accident or Incorrect Electrical Voltage and Curr...

Page 10: ...lephone wire both 10 long Install the sensors at a location so that they will be exposed to the fresh air intake ex the fresh air ductwork Drill 2 3 4 diameter holes spaced appropriately and install the sensors with the provided hardware NOTE the sensor wires can be extended up to 300 feet without deviation Use appropriate duct tape to seal joints openings as necessary DIMENSIONS in SCREEN DIAGRAM...

Page 11: ... to 55 C High Limit Temperature settings range 65 105 F 18 C to 40 C Low Limit Temperature settings range 20 60 F 6 C to 16 C Heater Temperature settings range 32 F 62 F 0 C 16 C Temperature resolution 1 F or 0 5 C Temperature Accuracy 1 F or 0 5 C Humidity measurement range 10 95 High Limit Humidity settings range 55 90 Low Limit Humidity settings range 10 50 Humidity resolution 1 Humidity Accura...