MODBUS message
Direction
Function
Dates
CRC verifi cation
8 bits
8 bits
N x 8bits
16 bits
Format for each byte in RTU mode is:
• System codes: 8–bit binary
• Bits per Byte: 1 bit to START (start)
8 bits for data, the most signifi cant bit is sent fi rst
1 bit for parity (Even parity is required)
1 bit for STOP (end)
8.2. MODBUS MEMORY MAP
Holding registers
N°REG.
Register
Min. Max.
Description
Default
Comments
0
TipoMotor
0
1
0=AC
1=DC
1
Motor type
1
ModoFun
0
7
0=PI_Presión
1=PI_Caudal
2=Proporcional
3=Max-Min
4=PI_Presión+RTC
5=PIRTC
6=PropoRTC
7=Max-Min+RTC
0
Operation mode
2
SensorPI
0
4
0=Interno
1=IN1 0-10V
2=IN1 4-20mA
3=IN2 0-10V
4=IN2 4-20mA
0
Sensor type in PI
PRESSURE or PI VOLUME
mode
3
Sensor1
0
7
0=NO
1=0-10V %HR
2=4-20mA %HR
3=0-10V °C
4=4-20mA °C
5=0-10V CO2
6=4-20mA CO2
7=NTC 100K
0
Sensor type in
PROPORTIONAL mode
and analog input signal 1
4
Sensor2
0
6
0=NO
1=0-10V %HR
2=4-20mA %HR
3=0-10V °C
4=4-20mA °C
5=0-10V CO2
6=4-20mA CO2
0
Sensor type in
PROPORTIONAL mode
and analog input signal 2
5
PIRange
50
50
100
1250
2500
9900
SensorPI=0
SensorPI<>0
Sensor<>0
400Pa
Range sensor in PI
PRESSURE mode
6
SetPoint
0
5
0=Interno
1=IN1 0-10V
2=IN1 4-20mA
3=IN2 0-10V
4=IN2 4-20mA
5=ConsolaMODBUS
(PROSYS ECOWATT)
5
Set point in PI PRESSURE
mode
7
Kp
1
250
Increases 1
20
Proportional constant in PI
PRESSURE mode
8
Ki
1
250
Increases 1
20
Integral constant in PI
PRESSURE mode