PARAMETERS
< Kp=100 OK
Press
or
to manually modify this parameter.
It is advised not to modify.
PARAMETERS
< Ki=20 OK
Press
or
to manually modify this parameter.
It
is advised not to modify.
SENSOR IN1
<SIN SENSOR OK
Press
or
to manually modify this parameter.
It
is advised not to modify.
SP-2 PRESSURE
< 50% OK
Press
or
to manually modify this parameter.
This value corresponds to the % of pressure set point
being the fan in night mode. To connect a time clock or
potential-free switch to the digital input J11
DIGITAL INPUT
< (NC) OK
DIGITAL INPUT
< (NO) OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Digital input:
- NC:
Normally closed contact. The fan will pass to night mode when contact is opened.
- NO:
Normally open contact. The fan will pass to night mode when contact is closed.
OUTPUT PULSES
< 4 OK
Press
or
to manually modify parameter that
displays the speed by J8 output (TACOM).
It is advised
not to modify
.
OK
OK