![S&P CTB ECOWATT Installation Manual. Instructions For Use Download Page 45](http://html1.mh-extra.com/html/sandp/ctb-ecowatt/ctb-ecowatt_installation-manual-instructions-for-use_3144131045.webp)
ENGLISH
45
MOTOR TYPE
< EC OK
ENTER PASSWORD:
1 1 1 OK
Enter the password
Default: 1 1 1
CHANGE PASSWORD
SI
NO
It is possible to assign a new password to your device
(channel)
No modify
OK
OK
OK
OK
OK
OK
SENSOR
< INTERNAL OK
SENSOR
<IN1 0-10V OK
SENSOR
<IN1 4-20mA OK
SENSOR
<IN2 0-10V OK
SENSOR
<IN2 4-20mA OK
OK
OK
Sensor: Sensor type
-
INTERNAL:
Pressure differential internal sensor
- IN1 0-10V:
External sensor with analog signal 0-10V (J5 terminal)
- IN1 4-20mA:
External sensor with analog signal 4-20mA (J5 terminal)
- IN2 0-10V:
External sensor with analog signal 0-10V (J6 terminal)
- IN2 4-20mA:
External sensor with analog signal 4-20mA (J6 terminal)
RANGE
< 400Pa OK
Press
or
to manually modify the parameter.
The value displayed corresponds to the scale of the
internal sensor factory pre-set. In an external sensor is
installed, introduce the corresponding range.
SET POINT
< INTERNAL OK
SET POINT
<CONSOLE OK
SET POINT
<IN1 0-10V OK
SET POINT
<IN1 4-20mA OK
SET POINT
<IN2 0-10V OK
OK
OK
OK
OK