TECHNICAL CHARACTERISTICS
Power supply should conform to safety Standard in force in your country.
Check that the earth connection has been done correctly. The motor is fitted with internal heat protection.
Version with lock-isolating switch
Cabinet fan + hot water coil + filter :
Cabinet size
CAIB 10
CAIB 17
CAIB 24
CAIB 35
Weight (kg)
40
40
55
57
Single phase 230V 2-speed motor:
Maximum absorbed
power (W)
300
460
740
1175
Current HS/LS (A)
1.4/1.1
2.1/1.7
3.7/2.0
4.8/3.3
Speed (rpm)
2050
1150
1200
1250
Cable glands (ISO)
M20
M20
M20
M20
Terminal box connection
capacity (mm²)
6²
6²
6²
6²
Version with integrated controller
Cabinet fan + hot water coil + controller :
Cabinet size
CAIB 10
CAIB 17
CAIB 24
CAIB 35
Weight (kg)
40
40
55
57
Voltage (V)
Mono 230V
Absorbed current (A)
1,5
2,2
3,8
5,0
Maximum absorbed
power (W)
310
450
750
1190
Cable glands (ISO)
M25
M25
M25
M25
Terminal box connection
capacity (mm²)
6²
6²
6²
6²
Control terminals ( "Boost" demand, room temperature sensor...)
Cable glands (ISO)
M20
M20
M20
M20
Terminal box connection
capacity (mm²)
2.5²
2.5²
2.5²
2.5²