10.1.3. Temperature control (DI and DC versions)
In models with post-heating (DI and DC), the Termo-Reg unit performs temperature control.
For this purpose, depending on requirements, the opening or closing of the By-pass and the
use or not of the post-heating battery is managed.
First priority is given to reach the temperature set by opening or closure of the By-pass. In
case of if not suffi ciently proceed activation of the post-heating battery.
The temperature taken as reference control is selectable
between supply temperature (contribution to local) and ex-
traction temperature (indoor environment). (See settings in
installer mode)
By default, the control is set to control the supply tempera-
ture (contribution to local).
By pressing the TEMPERATURE button is possible choose
between low, medium or high temperature.
An LED indicates the selected temperature.
The user can select 3 different levels of temperature inside of a certain range of values. There
are 3 ranges of temperature: ºC 17/20/23, 20/23/26 and 23/26/29ºC. By default, the predefi ned
temperature range is ºC 20/23/26. To change this temperature range must be accessed in
installer mode.
To turn off the heating mode, press the TEMPERATURE button until all 3 temperature leds
are off.
10.1.4. Drive By-pass
The By-pass function allows (By-pass closed) or by-passes
(open By-pass) the passage of air through the heat exchanger.
The By-pass has two modes of operation:
•
Manual:
The By-pass can be selected to always remain
open or closed.
•
Automatic:
In this mode the control will decide, depending
the values of the various temperature sensors and tem-
perature setpoint, whether open or close the By-pass as
there is demand for warm or cooler air. Below 15ºC the
By-pass will always remain closed to prevent low supply
temperatures.
AUTOMATIC
BY-PASS
(ON)
AUTOMATIC
BY-PASS
(OFF)
MANUAL
BY-PASS
BY-PASS
OFF
HIGH
26°C
MEDIUM
23°C
LOW
20°C
CALEF.
OFF
Summary of Contents for CADB-N 05 TERMO-REG
Page 2: ......
Page 16: ...16 ESPA OL Versi n DI con by pass Versi n DC con by pass...
Page 45: ...45 ENGLISH DI Version with By pass DC Version with By pass...
Page 74: ...74 FRAN AIS Version DI avec by pass Version DC avec by pass Accessoire Accessoire...
Page 91: ...91 ALIMENTACION 230V 50Hz CADB N D 12 18 23 30...
Page 92: ...92 ALIMENTACION 400V 50Hz 3Ph N CADT N D 45 55 80...
Page 93: ...93 ALIMENTACION 230V 50Hz CADB N DC C5 08...
Page 94: ...94 ALIMENTACION 230V 50Hz CADB N DC 12 18 23 30...
Page 95: ...95 ALIMENTACION 400V 50Hz 3Ph N CADB N DC 45 55 80...
Page 96: ...96 ALIMENTACION 230V 50Hz CADB N DI 05 08...
Page 97: ...97 ALIMENTACION 230V 50Hz CADB N DI 12...
Page 98: ...98 ALIMENTACION 400V 50Hz 3Ph N CADB N DI 18 23 30...
Page 99: ...99 ALIMENTACION 400V 50Hz 3Ph N CADT N DI 45 55 80...