7.5. CONNECTIONS
7.5.1. Piping and duct connections
7.5.1.1. Connection with air duct
The fans are always blowing out with regard to the machine. Before making the connection of air
lines, verify existing identifi cation labels in each mouth of the heat recovery units.
7.5.1.2. Connecting the water coil piping. DC Versions
Connecting the unit to the water network
- Maximum pressure: 31.62 bar
- Maximum temperature: 150°C
• Water coils of DC versions have threaded connections. Secure the coil manifold with the ap-
propiate tool when tightening the threads. This will prevent the force from being transmitted
to the manifold, which can damage it.
• The following table indicate the size and type o thread used on water coils for DC versions:
CADB/T-N MODEL
THREAD
05 / 08
1/2”
12
3/4”
18,23 y 30
1”
45 y 55
1 1/4”
80
1 1/2”
• To ensure the installation on a hand, it is essential that the installation includes the following
elements:
- Unit intake pre-fi lter that traps suspended particulate matter.
- Bleed valves should be fi tted at each of the high points in the installation.
Summary of Contents for CADB-N 05 TERMO-REG
Page 2: ......
Page 16: ...16 ESPA OL Versi n DI con by pass Versi n DC con by pass...
Page 45: ...45 ENGLISH DI Version with By pass DC Version with By pass...
Page 74: ...74 FRAN AIS Version DI avec by pass Version DC avec by pass Accessoire Accessoire...
Page 91: ...91 ALIMENTACION 230V 50Hz CADB N D 12 18 23 30...
Page 92: ...92 ALIMENTACION 400V 50Hz 3Ph N CADT N D 45 55 80...
Page 93: ...93 ALIMENTACION 230V 50Hz CADB N DC C5 08...
Page 94: ...94 ALIMENTACION 230V 50Hz CADB N DC 12 18 23 30...
Page 95: ...95 ALIMENTACION 400V 50Hz 3Ph N CADB N DC 45 55 80...
Page 96: ...96 ALIMENTACION 230V 50Hz CADB N DI 05 08...
Page 97: ...97 ALIMENTACION 230V 50Hz CADB N DI 12...
Page 98: ...98 ALIMENTACION 400V 50Hz 3Ph N CADB N DI 18 23 30...
Page 99: ...99 ALIMENTACION 400V 50Hz 3Ph N CADT N DI 45 55 80...