background image

 

Figure 5. SpeedNet Radio Ethernet interface Pinout (RJ-45). 

 

 

 

Pin Function 

Description 

TXD+ Transmit 

2 TXD- 

Transmit 

3 RXD+ 

Receive 

4 NC 

No 

Connection 

5 NC 

No 

Connection 

6 RXD- 

Receive 

7 NC 

No 

Connection 

8 NC 

No 

Connection 

Need Types of installation inserted here:  

IR Internal 

Repeater 

- pole 

- streetlight 

- gateway 

 

Need photos and diagrams. 

INSTALLATION 

Installation Types 

 

Connection Cables 

• 

Connect antenna to SpeedNet Radio. 

• 

Connect Ethernet cable to SpeedNet Radio and PC used for configuration.  

• 

Connect power supply to the SpeedNet Radio. 

Cable Installation 

1072-510 

15 

Summary of Contents for SpeedNet

Page 1: ...Messages 3 Following Safety Instructions 3 Replacement Instructions and Labels 3 Section Page INSTALLATION Overview 4 Pre Installation Checklist 4 IP Setup 4 Network Example 8 Routing Options 10 Regu...

Page 2: ...t Support Product Support Documents Documents are posted in PDF format The standard warranty contained in S C s standard conditions of sale as set forth in Price Sheet 150 applies to the S C SpeedNet...

Page 3: ...ded precautions are not followed CAUTION CAUTION identifies hazards or unsafe practices which can result in minor personal injury or product or property damage if instructions including recommended pr...

Page 4: ...the source node in their route tables If a receiving node is either the destination node or has stored a route to the destination with a corresponding sequence number greater than or equal to that con...

Page 5: ...dress class by examining the first 4 bits of the IP address Class A addresses begin with Oxxx or 1 to 126 decimal Class B addresses begin with IOxx or 128 to 191 decimal Class C addresses begin with 1...

Page 6: ...00011010 11110000 11001000 172 26 240 200 Class B IP Address 11111111 11111111 00000000 00000000 255 255 000 000 Default Class B Subnet Mask 10001100 00011010 00000000 00000000 172 26 000 000 Network...

Page 7: ...etworks 7 1072 510 OSI Model Data Unit Layer Function Data Application Network process to application IntelliRupter IntelliTEAM Presentation Data representation and encryption Session Interhost commun...

Page 8: ...c is routed between Ethernet segments Figure 1 Multi Network SpeedNet Radio Example with Automatic Switch Controls lED Once the individual data networks are established it is recommended that you plan...

Page 9: ...INSTALLATION 9 1072 510 1072 510 Figure 2 Example of a Network Using SpeedNet AODV...

Page 10: ...ally update the route tables as the network topology changes For environments where routes are required to change dynamically AODV is typically the best Ad Hoc Routing mode to choose Using Static Rout...

Page 11: ...table The SpeedNet Radio from Subnet 2 must have a static route to Subnet 1 using the SpeedNet Radio from Subnet 1 as the gateway This route should be set up like this 192 168 1 0 Network 255 255 255...

Page 12: ...4 2 and 17 4 3 as well as the American National Standards Institute ANSI in 4 1 of IEEE Standard for Safety Levels with Respect to Human Exposure to Radio Frequency Electromagnetic Fields 3kHz to 300...

Page 13: ...common antenna cables Table 1 Antenna Cable Loss Type of Antenna Cable Loss per 100 of Cable LMR 400 3 9 dB LMR 600 2 5 dB LMR 900 1 7 dB Table 2 Antenna Cable Loss Examples with LMR 400 Cable Antenna...

Page 14: ...les always verify cable loss prior to installation NOTE Table 4 assumes 1 watt output power from the SpeedNet Radio Antenna Gain Cable Type length loss EIRP 8 2 dBi 135 LMR 900 2 3 dB loss 35 9 dBm 10...

Page 15: ...NC No Connection 8 NC No Connection Need Types of installation inserted here IR Internal Repeater pole streetlight gateway Need photos and diagrams INSTALLATION Installation Types Connection Cables C...