background image

1011-540  5-17-04

Operation

15

S&C Electric Company 

BankGuard PLUS 

Proprietary Information

Control

value, the appropriate control action is taken. The control will lockout the bank if the 
“Gross Over Voltage Level” or the “Lockout Level” setpoint value is exceeded. Or issue 
an alarm if the “Alarm Level” setpoint value is exceeded.

Ungrounded Wye Shunt Reactors

The BankGuard PLUS Automatic Control Device provides protection of ungrounded, 
wye-connected shunt reactors (Figure 5), either 3-phase reactors or 3-phase banks of 
single-phase reactors. The control device detects turn-to-turn faults in the windings of 
these shunt reactors, the most common mode of reactor failure. When a developing turn-
to-turn fault occurs in any phase winding, the shunt reactor is protected from further 
damage by automatic switching provided by the control device. The control device locks 
out the entire shunt reactor when the neutral-to-ground voltage exceeds the calculated 
level. (See the Setup Instruction Sheet 1011-530 for more details.) In general, you should 
enable the unbalance compensation feature if the magnitude of the calculated error voltage 
caused by inherent reactor unbalance resulting from manufacturing-tolerance variations 
among the phase windings approaches 50% of the desired lockout-level setting.

For ungrounded, wye-connected shunt reactors, the control device uses an analog input 
and digital voltmeter to detect the reactor neutral-to-ground voltage, as monitored by an 
S&C 15-Volt-Ampere Potential Device. A digital filter attenuates harmonics and noise.

When the Unbalance Compensation feature is disabled, the magnitude of the real-time 
neutral-to-ground voltage is compared with the “Gross Over Voltage Level”, “Lockout 
Level”, and “Alarm Level” setpoint values, if enabled. Reactor-turn failures will cause the 
real-time neutral-to-ground voltage magnitude to change. If the real-time neutral-to-
ground voltage magnitude exceeds a setpoint value continuously for a time greater than 
the applicable time delay setpoint value, the appropriate control action is taken. The 
control will lock the reactor out if the “Gross Over Voltage Level” or the “Lockout Level” 
setpoint value is exceeded. The control will issue an alarm if the “Alarm Level” setpoint 
value is exceeded.

In addition to the neutral-to-ground potential device, one 30-Volt-Ampere S&C Potential 
Device is required to be installed on any one of the line phases to obtain a reference angle 
when the Unbalance Compensation feature is set to “Reactor” only. During the setup of 
the Unbalance Compensation feature, a neutral-to-ground voltage magnitude sample and a 
reference angle (Aref) sample are used to obtain and store an approximate magnitude 
correction value (see Signal Processing below for an explanation of how the value is 
calculated). Setup of the Unbalance Compensation feature should be accomplished during 
a time when any voltage unbalances caused by the loads are minimal. During each control 
cycle, the stored, approximate magnitude correction value is subtracted from the real-time 
neutral-to-ground voltage magnitude to obtain a compensated neutral-to-ground voltage 
magnitude. Reactor -turn failures will cause the real-time neutral-to-ground voltage 
magnitude to change and, therefore, change the compensated neutral-to-ground voltage 
magnitude. The control compares the compensated neutral-to-ground voltage magnitude 
with the “Gross Over Voltage Level”, “Lockout Level”, and “Alarm Level setpoint values, 
if enabled. If the compensated neutral-to-ground magnitude exceeds a setpoint value 

Summary of Contents for BankGuard PLUS

Page 1: ...1011 540 5 17 04 BankGuard PLUS Control Operation Instructions S C Electric Company 6601 North Ridge Blvd Chicago Illinois 60626 USA...

Page 2: ...duct Support Documents Documents are posted in PDF format Safety Information WARNING The equipment covered by this publication must be installed operated and maintained by qualified persons who are kn...

Page 3: ...anding Safety Alert Messages There are several types of safety alert messages which may appear throughout this instruction sheet as well as on labels attached to the BankGuard PLUS Control Familiarize...

Page 4: ...le by contacting your nearest S C Sales Office S C Headquarters or S C Electric Canada Ltd Instruction Sheet Contents Introduction 5 Applicable Software 5 Control Device Hardware and Software 6 Intell...

Page 5: ...e 9 z Generating reports page 21 z Saving and loading setup configurations page 22 z Viewing the IntelliLINK software without data page 23 z Creating and using snapshots VM files page 24 z Updating th...

Page 6: ...buttons which allow you to monitor the capacitor bank reactor and the control device It also includes a liquid crystal display and buttons for scrolling and selecting data Figure 1 Location of BankGua...

Page 7: ...or SCADA master station and other conditions The Control Device software and the setpoint values are all stored in non volatile control device memory This memory survives power interruptions The memo...

Page 8: ...nications equipment can be mounted near the control device This eliminates clutter and provides a higher level of reliability for the overall installation DNP 3 0 is the standard protocol for the BAnk...

Page 9: ...acitor unit operating time at varying per unit multiples of the capacitor nameplate voltage rating This curve applies for up to 300 applications of power frequency overvoltages of the magnitude and du...

Page 10: ...s before the control device locks out the bank This lets you readily locate the failed capacitor unit The BankGuard PLUS Automatic Control Device includes a standard alarm function which provides an a...

Page 11: ...raneous voltages can introduce significant errors in or even overpower the voltage signal created by the loss of individual capacitor units For example a fixed error voltage may be present due to inhe...

Page 12: ...of the error voltage caused by system voltage imbalances and or inherent capacitor bank imbalances approaches 50 of the value of the neutral to ground voltage calculated for one isolated capacitor un...

Page 13: ...tage unbalances caused by the loads are minimal During each control cycle the stored approximate magnitude correction value is subtracted from the real time neutral to ground voltage magnitude to obta...

Page 14: ...t to neutral voltages to change If the real time magnitude of the sum exceeds a setpoint value continuously for a time greater than the applicable time delay setpoint value the appropriate control act...

Page 15: ...ared with the Gross Over Voltage Level Lockout Level and Alarm Level setpoint values if enabled Reactor turn failures will cause the real time neutral to ground voltage magnitude to change If the real...

Page 16: ...stem imbalances is provided During the setup of the unbalance compensation feature a neutral to ground voltage magnitude sample a sum of the line voltages sample and the reference angle are used to ca...

Page 17: ...ardware samples the sensor s analog output waveform and then converts the samples to digital values Figure 6 The control s software processes the digital values using a Discrete Fourier Transform algo...

Page 18: ...ain a compensated neutral to ground voltage magnitude The compensated neutral to ground voltage magnitude is then compared to the setpoint value s If the compensated neutral to ground voltage magnitud...

Page 19: ...s V tap sum and the value of the phase angle Aref between the tap point voltages sum and the reference line voltage Using the Law of Cosines an approximate corrected magnitude is obtained utilizing th...

Page 20: ...BankGuard PLUS S C Electric Company Control Proprietary Information 20 Operation 1011 540 5 17 04 Figure 9 Approximate Corrected Magnitude...

Page 21: ...orts 3 In the dialog box select the type of report you want to generate then click OK There are four kinds of reports z Full Includes all the information contained in the control device z System Setup...

Page 22: ...Setpoints dialog box specify a name and location for this configuration file then click Save If you do not specify a location the file is saved to the same directory as the program files for this for...

Page 23: ...nd Help file without connecting to a control device or a snapshot 1 Start the IntelliLINK software on your computer 2 During startup click Cancel to close the Connect dialog box If the IntelliLINK sof...

Page 24: ...can skip this step 2 From the File menu choose Save Snapshot 3 In the dialog box specify a file name and location for this snapshot then click Save If you do not specify a location the file is saved...

Page 25: ...control device which is in the field while you do not have access to a comparable device 1 Connect to the snapshot For details see View connect to a Snapshot on page 24 2 Change the configuration set...

Page 26: ...uter For details see To Start the IntelliLINK Software in the Setup Instruction Sheet 1011 530 2 Connect your computer to the LOCAL COMM PORT or optical port on the control device 3 Start the Update p...

Page 27: ...follow the progress in the lower right corner of the window Once the update is complete the window automatically closes CAUTION NOTE If the software on the disk is not the same type as the software in...

Page 28: ...BankGuard PLUS S C Electric Company Control Proprietary Information 28 Operation 1011 540 5 17 04...

Reviews: