background image

  

  INSTRUCTION SHEET

  

716-600

Page 17 of 24

February 11, 2002

S&C ELECTRIC COMPANY

INTERRUPTER REPLACEMENT ON MODELS 2010, 2015, AND 2040 — Continued

Step 31

Replace the access cover retained from Step 20 and
securely tighten the associated 

⁵⁄₁₆

—18

³⁄₄

 hex-head

stainless-steel cap screws.

Step 32

Remove the shield for the pressure-relief device and low-
gas-pressure indicator from the replacement interrupter.
Discard the shield and its hardware. Reconnect the high-
voltage conductor to the interrupter-end terminal pad
and, on Model 2040, to the transition-box-end terminal
pad.

Step 33

Remove the container from the replacement interrupter
as follows:

(a) Remove and discard the 

³⁄₈

—16 zinc-plated serrated

hex nuts which run the length of the container.

(b) Remove and discard the 

³⁄₈

—16

⁷⁄₈

 and two

³⁄₈

—16

1

 zinc-plated hex-head cap screws and flat

washers which attach the 

upper

 container-half to the

coupling end casting of the interrupter. Also remove
and discard the 

³⁄₈

—16

⁷⁄₈

 and two 

³⁄₈

—16

1

 zinc-

plated hex-head cap screws and flat washers which
attach the upper container-half to the indicator end
casting of the interrupter. 

(c) Pry the container-halves apart with a screwdriver. The

upper container-half can now be removed and dis-
carded—slotted holes are provided so that a rope or
lifting sling can be attached and the container-half
more conveniently lowered to the ground. 

(d) Now remove and discard the 

³⁄₈

—16

⁷⁄₈

 hex-head

cap screw and flat washer which attach the 

lower

 con-

tainer-half to the coupling end casting of the inter-
rupter, and the 

³⁄₈

—16

⁷⁄₈

 hex-head cap screw and

flat washer which attach the lower container-half to
the indicator end casting of the interrupter. Then dis-
card this container-half.

(e) Finally, remove and discard the foam-core inner liner

wrapped around the interrupter.

Step 34

Replace the trip-circuit and control-circuit fuseholders in
the operator or—on newer operators—close the control-
source disconnect switch and replace the motor-and-
closing circuit fuseholder.

Step 35

Attach lifting slings to the four lifting rings on the
replaced interrupter container. 

Do not

 loop slings from

one end of the container to the other. Carefully lift the
interrupter into the replacement interrupter shipping
crate. Secure the interrupter and close the lid. 

Step 36

Ship the replaced interrupter, transportation charges
prepaid, to S&C Electric Company, Repair Center, 1800
Devon Avenue, Chicago, Illinois 60660-1010. To ensure
proper handling, purchasers are asked to obtain from the
nearest S&C Sales Office a special serially numbered
label to place on the shipping crate. Please enclose a
packing slip showing purchase order or requisition
number covering the exchange. 

Summary of Contents for 2000 series

Page 1: ...e containing sulfur hexafluoride SF6 gas under pressure It employs an operating rod which is driven to the open position at high speed by means of a power train connected to the Series 2000 Circuit Sw...

Page 2: ...binet of the circuit switcher using the instruction manual holder Proper Application Warranty The standard warranty contained in S C s standard con ditions of sale as set forth in Price Sheet 150 is a...

Page 3: ...ffice S C Authorized Distributor S C Headquarters or S C Electric Canada Ltd It is important that any missing damaged or faded labels on the equipment be replaced immediately Replacement labels are av...

Page 4: ...of loss and or damage Packing The Series 2000 Circuit Switcher interrupter is a porce lain enclosed hermetically sealed device containing sulfur hexafluoride SF6 gas under pressure 75 PSI To guard aga...

Page 5: ...ound the interrupter to be replaced using the following procedure a Remove the two container halves from the shipping crate Note that one of the container halves is fur nished with a loosely attached...

Page 6: ...r forth as necessary to allow the cable to be threaded through the holes g Pull the cable taut at the indicator end of the inter rupter and attach two of the clamps furnished See Figure 3 right Secure...

Page 7: ...ith a black yellow striped label and spacer marked with a black yellow striped label to the interrupter using the 18 2 hex head stainless steel screw fur nished These items are included with the repla...

Page 8: ...d link Pin retaining clip 18 2 hex head stain less steel screw Stop bracket marked with a black yellow striped label 18 2 hex head stain less steel screw Coupling Slot coincides with cross hole Spacer...

Page 9: ...n box on the insulating support column Use care to avoid damaging the exposed coupling Step 10 Prepare the replacement interrupter for attachment to the insulating support column as follows a Remove a...

Page 10: ...38 kV Insert the connecting pin retained from Step 10 c into the coupling and operating rod link See Figure 5 top It will be necessary to loosen the 18 2 hex head stainless steel screw indicated in Fi...

Page 11: ...wo 16 1 and one 16 zinc plated hex head cap screws and flat washers which attach one of the container halves to the indicator end casting of the interrupter Don t remove the remaining 16 cap screw it...

Page 12: ...ise the container into position around the interrupter d Using a screwdriver as necessary to spread the edges snap the two halves together as shown in Figure 3 Place a 16 zinc plated serrated hex nut...

Page 13: ...cover to the side of the transition box on the insulating support column See Figure 10 Remove the cover and place it and the hardware on a clean surface They will be re used in Step 31 Step 21 Prepar...

Page 14: ...rate Step 26 Remove the interrupter lifting bracket and associated inch stainless steel hardware from the end of the replacement interrupter This bracket is not used in the interrupter replacement pro...

Page 15: ...ing slings to the replacement inter rupter and carefully lift and slide the interrupter into posi tion Use care to avoid damaging the exposed operating rod Thoroughly wire brush the mating surfaces on...

Page 16: ...draw it approximately inch so that the connect ing pin can be inserted Do not remove the screw at this time Now insert the pin retaining clip retained from Step 28 as indicated in Figure 13 left Make...

Page 17: ...e provided so that a rope or lifting sling can be attached and the container half more conveniently lowered to the ground d Now remove and discard the 16 hex head cap screw and flat washer which attac...

Page 18: ...cable Do not remove the shorting plug from the end of the green 6 pin connector at this time See Figure 14 Step 38 On Circuit Switchers with vertical interrupters Model 2020 Model 2025 and Model 2030...

Page 19: ...he side of the operating rod that is towards the access opening Feeding the sensor cable from behind the operat ing rod may cause the cable to catch on the rod during switch operation See Figure 16 St...

Page 20: ...nnector located on the red sensor cable Remove the shorting plug from the 6 pin socket on the transmitter circuit board Firmly plug the green 6 pin connector from the inter rupter into the green 6 pin...

Page 21: ...e replaced Retain the jumper for future use in the pocket on the operator enclosure door NOTICE Save the shorting plugs and install them on the replaced interrupters When replacing an interrupter with...

Page 22: ...perator door Step 46 Press and hold for 10 seconds the system set up button located on the right side of the receiver See Figure 20 The receiver unit will start to count down See Figure 21 Release the...

Page 23: ...nce every hour When the magnet tool is applied to transmitter the transmitter is prompted to send a signal to the receiver once every second The transmitter will continue to send this sig nal for up t...

Page 24: ...esignations are not correct reprogramming of the receiver is required Repeat Steps 41 51 until the pole unit designations are appropriate for the installation NOTICE If the poles are not initialized i...

Reviews: