4.3 MAIN Screen Operation & Setting
MENU KEY
FUNCTION
SET KEY
SUB SET setting
MAIN MENU
FUNCTION
SUB SET
SET KEY
SUB SET1, SUB SET2 (PAGE UP/DOWN KEY)
OPER MODE : FIX / PROG
PWR MODE : State mode after power failure
Can be recognized over 3 sec. power failure
If power on within 3 sec. It is automatically running
with HOT mode
▶
STOP : After power failure, go to STOP state
▶
COLD : After power failure, go to RUN on fix running or
go to SEG1 on program running.
▶
HOT : After power failure, running by previous data before
power failure.
KEY LOCK : Set key in possible / impossible
▶
ON : Lock(Key in impossible)
▶
OFF : Unlock(Key in possible)
BUZZER : Set buzzer sound ON/OFF
FUZZY : Set FUZZY ON/Off(Fuzzy : Overshoot suppressing
function)
FIX OP TM : Set FIX Operation time ON/OFF
It is reserving function within 9999 hours and fix
running is finishing after set the time.
TEMP(HUMI) SLOP : Set the slop for TSP, it is increase/decrease
to the target temp/humi gradually.
4.3.1 FUNCTION
(Figure 1 : Overshoot suppressing function by FUZZY)
(Figure 2 : Ex. SLOPE setting)
SP
PV : FUZZY OFF
PV : FUZZY ON
SP=100℃
SP=40℃
Temp gap 60℃
Upping time 1min.
Change SP
60℃/1min.
Rate up
=60/1=60(℃/min)