Wait
The wait function holds off the transition of segment until deviation is cleared up. The use of this
function is enabled by defining a wait zone that is a deviation range to determine the follow-up of PV
data input, and a wait time, which is a period of waiting time until PV data enters the wait zone. When
PV input enters the wait zone within the wait time, the operation shifts to the next.
If not, the shift takes place as soon as the wait time is over, The WTM should be set for prevent to
infinite waiting
Running Wait
(Time stop)
WZ
WZ
WTM
Segment_n
Segment_(n+1)
Segment_(n+2)
The time on release waiting,
Running with next
segment(n+1)
SP
PV
(Figure 3 : WAIT - Ex. Wait Function Release Within WTM)
WZ
WZ
WTM
SP
PV
(Figure 4 : WAIT - Ex. PV can
’
t enter the wait zone within WTM)
Running Wait
(Time stop)
The time on release waiting,
Running with next
segment(n+1)
Segment_n
Segment_(n+1)
Segment_(n+2)
WAIT TIME
WAIT TIME(HH.MM)
0.00 ∼ 99.59
ABS
0.00
Always
OFF, ON
ABS
OFF
Always
WAIT USE
WAIT USE
ON, OFF
ABS
OFF
Always
PT A.CLR
SEG A.CLR
ALL PATTERNS DELETE
ALL SEGMENTS DELETE
OFF, ON
ABS
OFF
Always
O
O
O
O
Symbol
Parameter
Range
Display
Unit
Default
Edit