THERMOCOUPLE WIRING
The following rules need to be followed when wiring the thermocouple temperature
sensors from the Thermocouple to the Heater electrical panel. The signal from the
temperature sensor is 4-20mA DC.
•
Always
use shielded, 2 conductor cable from the thermocouple to the control panel
terminal blocks. Terminate the shield only on the electrical panel end. Do not use
Type J thermocouple wire for hookup.
•
Never
run the shielded sensor wires with the power wiring (including 120 VAC
control wires). You can run several shielded 4-20mA shielded wires together in the
same conduit with other wires marked sensitive on the external connection diagram.
Part No. 21708 Type ‘J’
Thermocouple shown with
4-20mA Transmitter in junction
head.
Connect 4-20mA signal wires to
control cabinet to terminals 1
(+)
, 2
(-)
.
Red
(-)
wire from Thermocouple
junction goes to terminal 6.
White
(+)
goes from Thermocouple
junction goes to terminal 4.
Summary of Contents for HG-1-1501
Page 1: ...HG 1 1501 1 Million Btu Hr Gas Fired Heater Service and Operation Guide...
Page 2: ...PAGE 1 of 46 HG 1 1501 GAS FIRED HEATER SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...
Page 35: ...PAGE 32 of 46 HG 1 1501 GAS FIRED HEATER SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...
Page 36: ...PAGE 33 of 46 HG 1 1501 GAS FIRED HEATER SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...
Page 38: ...PAGE 35 of 46 HG 1 1501 GAS FIRED HEATER SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...
Page 40: ...PAGE 37 of 46 HG 1 1501 GAS FIRED HEATER SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...
Page 41: ...PAGE 38 of 46 HG 1 1501 GAS FIRED HEATER SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...
Page 46: ...PAGE 43 of 46 HG 1 1501 GAS FIRED HEATER SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...
Page 47: ...PAGE 44 of 46 HG 1 1501 GAS FIRED HEATER SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...
Page 48: ...PAGE 45 of 46 HG 1 1501 GAS FIRED HEATER SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...