12-2-5 In case of heating at the cooling mode or cooling at the heating mode
1. Troubleshooting procedure
Change the setting temperature of
remote control.
Operate it with a heating mode
as soon as the defrosting is finished.
After 3 minutes, cooling
and heating start automatically.
No
No
No
Yes
Yes
Yes
Is the Thermo off?
Is the unit
in the defrosting operation?
Is the compressor
in 3 minutes off?
Check the resistance value
of 4-WAY valve coil.
Go to the next page
4-WAY valve main body error
Attach the
sensor correctly.
Over shortage
of the refrigerant
Connect the connecter
correctly.
4-WAY valve coil error
Exchange
the outdoor PCB.
No
Yes
Yes
Yes
OK
Yes
No
No
No
NG
No
Is much frost
in the indoor heat
exchanger?
Does the
4-WAY valve operate
normally?
Is the
outdoor air sensor and
outdoor heat exchanger attached
correctly?
Is the
4-WAY valve connector
connected correctly?
Dose the
voltage of AC 220V
apply to the connector of 4-WAY
valve coil during the
operation?
Troubleshooting
12-6
25888A(1)_1.indd 35
2006-04-14 ソタネト 2:26:12
Summary of Contents for UH035EAV Series
Page 46: ...MEMO Samsung Electronics 4 27 ...
Page 57: ...Samsung Electronics 5 11 5 3 Ass y Control Out UH035EAV DB93 03453A ...
Page 59: ...Samsung Electronics Ass y Control Out cont UH052EAV DB93 03665D UH070EAV DB93 03665E 5 13 ...
Page 106: ...Samsung Electronics MEMO 8 5 ...
Page 111: ...9 2 Refrigerating Cycle Diagram 9 5 Samsung Electronics EH035EAV UH035EAV ...
Page 112: ...Samsung Electronics EH052EAV UH052EAV EH070EAV UH070EAV Circuit Descriptions 9 6 ...
Page 164: ...Samsung Electronics 14 10 MEMO ...
Page 165: ...Samsung Electronics MEMO 14 11 ...